RS-422 Interface
Figure C.4
Note: 1. Turn on the DIP switch on the drive that is located at the end of the network. All other slave devices must have this DIP switch set to
the OFF position.
2. Set H5-07 to 0 when using the RS-485 interface.
Set H5-07 to 1 when using the RS-422 interface in multi-drop circuit. Set H5-07 to 0 when using the RS-422 interface in
point-to-point circuit.

◆ Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination resistor
that can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the
termination resistor by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not
located at the network line end.
Figure C.5
illustrates the setting of DIP switch S2.
To set the DIP switch on the terminal board, use an appropriate sized tool with a tip of approximately 8 mm (5/16 in.)
width.
Figure C.5
YEA_TM
only
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
R –
R+
PLC
S –
S+
IG
Figure C.4 RS-422 Interface
DIP Switch S2
OFF
ON
(OFF: default)
Figure C.5 Serial Communications Terminal and DIP Switch S2
C.3 Connecting to a Network
S –
Drive
S+
R –
S2
R+
IG
OFF
S –
Drive
S+
R –
S2
R+
IG
OFF
S –
Drive
S+
common_
R –
S2
R+
ON
IG
TMonly
S -
S+
RS-422
or
R -
RS-485
DIP
switch
R+
S2
Termination resistor (1/2 W, 120 Ω)
-
+
C
447