C.3 Connecting to a Network

C.3 Connecting to a Network
This section explains how to connect the drive to a MEMOBUS/Modbus network and the network termination required
for a connection.
◆ Network Cable Connection
Follow the instructions below to connect the drive to a MEMOBUS/Modbus network.
1.
With the power shut off, connect the communications cable to the drive and the master. Use terminals R+/S+ and
R–/S– for MEMOBUS/Modbus.
Figure C.2
Note: Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for the
communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485 communications,
connect S+ to R+, and S- to R- as shown in the diagram below.
2.
Check or set the termination resistor selection at all slaves. Use the description in
page 447
for slaves that are L1000A drives.
3.
Switch the power on.
4.
Set the parameters needed for serial communications (H5-01 through H5-11) using the digital operator.
5.
Shut the power off and wait until the display on the digital operator goes out completely.
6.
Turn the power back on.
7.
The drive is now ready to begin communicating with the master.
◆ Wiring Diagram for Multiple Connection
Figure C.3
and
Figure C.4
communication.
RS-485 Interface
Figure C.3
Note: 1. Turn on the DIP switch on the drive that is located at the end of the network. All other slave devices must have this DIP switch set to
the OFF position.
2. Set H5-07 to 1 when using the RS-485 interface.
446
YEA_co
mmon
P
M
Figure C.2 Serial Communications Cable Connection Terminals
explain the wiring diagrams for multiple connections using MEMOBUS/Modbus
R–
R+
PLC
S–
S+
IG
Figure C.3 RS-485 Interface
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
IG R+ R- S+ S-
S–
Send (–)
S+
Send (+)
R–
Receive (–)
R+
Receive (+)
IG
Shield Ground
S–
Drive
S+
R–
S2
R+
IG
OFF
S–
Drive
S+
R–
S2
R+
IG
OFF
S–
Drive
S+
R–
common_
S2
R+
ON
IG
TMonly
Network Termination on