2. Use the setdualpowerfeed(8) command to enable or disable the dual power
feed of this system.
<Example 1>
XSCF> setdualpowerfeed -s enable
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
<Example 2> Disabling the dual power feed.
XSCF> setdualpowerfeed -s disable
enable -> disable
NOTE: Dual power feed will be disabled the next time the platform
is powered on.
3. Confirm the new setting, and if it is correct, turn off the input power and then
turn on to apply the specified configuration. When you enabled the dual power
feed mode, you can apply the configuration by executing the rebootxscf(8)
command.
XSCF> showdualpowerfeed
disable -> enable
NOTE: Dual power feed will be enabled the next time the platform
is powered on.
4. Confirm whether the setting is valid after turning off/on the input power.
XSCF> showdualpowerfeed
Dual power feed is enabled.
4-24
SPARC Enterprise Mx000 Servers XSCF User's Guide • August 2009
Enabling the dual power feed.