Enabling A Power Supply Shutdown; Powering On The Power Supply Through The Cli; Replacing A Power Supply - Brocade Communications Systems MLX Series Installation Manual

Mlx series, netlron xmr series
Hide thumbs Also See for MLX Series:
Table of Contents

Advertisement

8

Replacing a power supply

Enabling a power supply shutdown

The power-off power-supply command allows you to shut down a power supply manually.
To shut down a power supply, enter the following command.
Brocade# power-off power-supply 3
This will Shutdown The Power Supply # 3
Are you sure? (enter 'y' or 'n'): y
ERROR: Power Supply # 3 is the Last Available in the system and will not be
shutdown.
To force the shutdown, please use keyword "forced"
Syntax: power-off power-supply [forced] <decimal>
The power-supply keyword allows you to shut down a power supply.
The <decimal> variable specifies a power supply index number.
The forced option forces the last power supply available in the system to shut down.The CLI will not
shut down the last power supply unless the forced option is used.

Powering on the power supply through the CLI

Use the power-on power-supply command to turn on a power supply that has been shut down.
A power supply will shut down due to flapping, or if a shutdown is enabled manually using the
power-off power-supply command. Refer to
To turn on a power supply that has shut down, enter the following command.
Brocade# power-on power-supply 1
AC Power Supply 1 is OK
The output example displays the status for power supply 1 as OK.
NOTE
If a power supply has shut down, power to the interface module will be lost. There will not be enough
power remaining in the system.
Syntax: power-on [power-supply <decimal>]
The <decimal> variable specifies a power supply index number.
Replacing a power supply
To replace a power supply, have the following items available:
DANGER
The power supplies are hot swappable, which means they can be removed and replaced while
the device is powered on and running. However, Brocade recommends that you disconnect the
power supply from its power source before removing and replacing the supply. The device can be
356
A new power supply (AC or DC), which you can order from Brocade
A small flat-blade or Phillips screwdriver (Brocade MLX-4 only)
"Enabling a power supply shutdown"
Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide
on page 356.
53-1002373-02