Brocade Communications Systems MLX Series Installation Manual page 313

Mlx series, netlron xmr series
Hide thumbs Also See for MLX Series:
Table of Contents

Advertisement

CAUTION
To ensure adequate bonding when attaching the ground lug, a minimum of 20 PSI of torque is
required to be applied to the mounting hardware used to attach the ground lug.
FIGURE 209
1
#4 AWG power supply wire
4. Reconnect the power lugs to the power supply unit.
5. Replace the safety cover. Refer to
FIGURE 210
6. Connect the wire to your DC power source, making sure to connect the -48V cable to the
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for
regulations.
Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide
53-1002373-02
Crimping the power supply wire in the lug
1
2
Attaching the safety cover
negative terminal on the power supply and the 0V cable to the positive terminal as marked on
the power supply.
NOTE
DC return must be isolated from the device ground (DC-I) when connecting to the power
supply.
Installing a Brocade NetIron XMR 32000 router
2
1
2
Power lug
Figure
210.
4
295