Terminal Connection Diagram And Explanation Of Terminals And Switch Settings - Hitachi SJ700D-3 SERIES Quick Reference Manual

Hide thumbs Also See for SJ700D-3 SERIES:
Table of Contents

Advertisement

2.2.1 Terminal connection diagram and explanation of terminals and switch settings

3-phase power supply
200 V class: 200 to 240 V +10%, -15%
(50/60 Hz ±5%)
400 V class: 380 to 480 V +10%, -15%
(50/60 Hz ±5%)
When connecting separate power
supplies to main and control
circuits, remove J51 connector
cables beforehand.
Default jumper position
(sinking type : FUF/FF)
Default jumper position
(source type : FEF)
Forward rotation
command
Intelligent input
(8 contacts)
Digital monitor output
(PWM output)
Thermistor
Frequency
setting circuit
0 to 10 VDC (12 bits)
500 to 2,000Ω
-10 to +10 VDC (12 bits)
4 to 20 mA (12 bits)
Analog monitor
output
(voltage output)
0 to 10 V (10 bits)
Analog monitor
output
(current output)
4 to 20 mA (10 bits)
R
S
T
R
Jumper
J51
T
R0
Power supply for
T0
control circuit
P24
PLC
CM
1
FW
8
7
6
1
FM
CM1
TH
H
O
O2
OI
L
AM
AMI
Chapter 2
POWER
ALARM
HITACHI
RUN
Hz
V
kW
A
PRG
%
STOP/
RUN
RESET
2
FUNC
STR
1
DC24V
10kΩ
DC10V
10kΩ
100Ω
Type-D grounding (for 200 V class model)
Type-C grounding (for 400 V class model)
(See page 2-12.)
2 - 7
Installation and Wiring
U
V
W
PD
DCL
(without jumper bar)
P
Jumper bar
RB
Braking resistor
(Models with 22kW
N
or less capacity )
BRD
The dotted line indicates
AL0
the detachable control
terminal board.
AL1
Intelligent relay output contact
AL2
(default: alarm output)
15
Intelligent output
(5 terminals)
11
CM2
SP
SN
100Ω
RS485
RP
For terminating
SN
resistor
Option 1
Option 2
M
Motor