Proline Prosonic Flow I 400 Modbus RS485
Parameter
Process variable current output
Current range output
Endress+Hauser
10.4.5
Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output 1
‣
Current output 1
Process variable current output
(0359–1)
Current range output (0353–1)
Lower range value output (0367–1)
Upper range value output (0372–1)
Fixed current (0365–1)
Damping current output (0363–1)
Failure behavior current output
(0364–1)
Failure current (0352–1)
Parameter overview with brief description
Prerequisite
–
–
Description
Select the process variable for
the current output.
Select current range for
process value output and
upper/lower level for alarm
signal.
Commissioning
→ 89
→ 89
→ 90
→ 90
→ 90
→ 90
→ 90
→ 90
Selection / User
Factory setting
entry
*
• Off
–
• Volume flow
• Mass flow
• Flow velocity
• Sound velocity
• Temperature
• Density
*
• Signal strength
• Signal to noise
*
ratio
*
• Acceptance rate
*
• Turbulence
• Electronics
temperature
• 4...20 mA NE
Depends on country:
(3.8...20.5 mA)
• 4...20 mA NE
• 4...20 mA US
(3.8...20.5 mA)
(3.9...20.8 mA)
• 4...20 mA US
• 4...20 mA (4...20.5
(3.9...20.8 mA)
mA)
• 0...20 mA (0...20.5
mA)
• Fixed value
89
Need help?
Do you have a question about the Proline Prosonic Flow I 400 and is the answer not in the manual?
Questions and answers