Commissioning
Parameter
Terminal number
Signal mode
0/4 mA value
20 mA value
Current span
Failure mode
Failure value
84
Parameter overview with brief description
Prerequisite
The measuring device is not
approved for use in the
hazardous area with type of
protection Ex-i.
In the Failure mode
parameter, the Defined value
option is selected.
10.4.6

Configuring the current output

The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
Current output 1 to n
Terminal number
Signal mode
Process variable current output
Current range output
Lower range value output
Upper range value output
Fixed current
Description
Shows the terminal numbers
used by the current input
module.
Select the signal mode for the
current input.
Enter 4 mA value.
Enter 20 mA value.
Select current range for
process value output and
upper/lower level for alarm
signal.
Define input behavior in alarm
condition.
Enter value to be used by the
device if input value from
external device is missing.
Proline Prosonic Flow G 300 HART
User interface / 
Factory setting
Selection / User
entry
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• Passive
Active
• Active
Signed floating-point
0
number
Signed floating-point
Depends on country
number
and nominal
diameter
• 4...20 mA (4...20.5
Country-specific:
mA)
• 4...20 mA NE
• 4...20 mA NE
(3.8...20.5 mA)
(3.8...20.5 mA)
• 4...20 mA US
• 4...20 mA US
(3.9...20.8 mA)
(3.9...20.8 mA)
• 0...20 mA (0...20.5
mA)
• Alarm
Alarm
• Last valid value
• Defined value
Signed floating-point
0
number
→  85
→  85
→  85
→  85
→  85
→  86
→  86