Proline Prosonic Flow P 500 HART
Parameter
Terminal number
Signal mode
0/4 mA value
20 mA value
Current span
Failure mode
Failure value
*
Visibility depends on order options or device settings
Endress+Hauser
Failure mode
Failure value
Parameter overview with brief description
Prerequisite
–
–
–
–
–
–
In the Failure mode
parameter, the Defined value
option is selected.
10.4.8
Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output
‣
Current output 1 to n
Terminal number
Signal mode
Process variable current output
Current range output
Description
Shows the terminal numbers
used by the current input
module.
Select the signal mode for the
current input.
Enter 4 mA value.
Enter 20 mA value.
Select current range for
process value output and
upper/lower level for alarm
signal.
Define input behavior in alarm
condition.
Enter value to be used by the
device if input value from
external device is missing.
Commissioning
→ 107
→ 107
User interface /
Factory setting
Selection / User
entry
• Not used
–
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• Passive
Passive
*
• Active
Signed floating-point
0
number
Signed floating-point
Depends on country
number
and nominal
diameter
• 4...20 mA (4...20.5
Country-specific:
mA)
• 4...20 mA NE
• 4...20 mA NE
(3.8...20.5 mA)
(3.8...20.5 mA)
• 4...20 mA US
• 4...20 mA US
(3.9...20.8 mA)
(3.9...20.8 mA)
• 0...20 mA (0...20.5
mA)
• Alarm
Alarm
• Last valid value
• Defined value
Signed floating-point
0
number
→ 108
→ 108
→ 108
→ 108
107