Troubleshooting - Generac Power Systems PWRcell Reference Manual

Hide thumbs Also See for PWRcell:
Table of Contents

Advertisement

Troubleshooting

The troubleshooting table below references the images and diagnostics contained in this section and in
Inverter.
Use the diagnostic practices in the order they are listed to solve problems. If unable to resolve functionality
call Generac PWRcell Technical Support 1-855-635-5186.
NOTE: Problems and diagnostics procedures are described in detail below.
Problem
Observed Symptoms
Multiple Inverter
Devices from one PWRcell system show up on
Systems Cross-
another. Multiple inverter or Beacon pages on one
Talking
inverter.
Inverter Error
Inverter home screen displays:
'
error detected on PWRcell [model]
No REbus Device
Inverter is enabled and REbus device (PV Link or
Comms
Battery) does not appear on inverter screen.
'N/A' on all device Icons at home screen and device
pages say 'offline'
Known device 'offline'- device page shows the device
but shows its status as 'offline'.
Beacon Device
Scrolling all the way through the device list on the
Page Missing
screen, using the left or right arrow keys, there is no
page for the REbus Beacon.
No Backup Power
Upon loss of utility grid power, system did not power
protected loads. Inverter may be in state: islanding,
waiting, standby, error.
Blackout /Brown-out Protected Loads lose power and come back on briefly
at intervals. Inverter screen says "Island Overload."
Stuck in Waiting or
Inverter will not connect to grid and will not export
Standby
power.
REbus Voltage is
Inverter will not bring up REbus and may be in states:
Low
low REbus voltage, waiting, standby, or error.
Stuck in Islanding
Inverter will not come out of islanded state
Stuck in Shutdown
Inverter will not come out of shutdown mode
Unknown Devices
Inverter screen shows unknown device pages where
Offline
device says it is
Configuration Error
Inverter device page shows "Configuration Error"
Diagnostic Repair Manual
Table 4-1. Inverter Troubleshooting
'
'
'
offline
Section 4 PWRcell Inverter
Diagnostics
PLM Cross-talk Recovery Proce-
– Refer to
dure
Appendix B Inverter
in
– Check Inverter Settings
– Disable/Enable
– Check REbus Fuses (after shutdown)
– Basic Function Test
– Check REbus DC Wiring
– Check AC Wiring
– Call Tech Support
– Check DC disconnect
– Check REbus DC Wiring Polarity
– Check Grounding
– Check REbus Fuses
– Power Cycle
– Check REbus fuses
– Verify DC Disconnect(s) ON
– Verify DC Disconnect(s) ON
– Check REbus Fuses
– Check USB connections at Beacon
– Check Beacon USB at Power Core
– Plug live Ethernet cable into Beacon
Internet Troubleshooting Flowchart
– See
– Ensure Protected Loads Breaker is ON
– Check Inverter Settings
– Check Protected Loads panel
– Check Battery
Island Overload
– See
.
– Check AC Wiring
– Call Tech Support
– Check AC wiring
– Check Inverter Settings
– Check REbus devices
– Basic Function Test
– Check Inverter Settings
– Check AC wiring
Stuck in Shutdown Mode
See
Unknown Devices
– Check Inverter Settings
Appendix B
.
'Offline'.
15