Generac Power Systems 04389-3, 04456-3, 04390-3 Installation And Owner's Manual

Generac Power Systems 04389-3, 04456-3, 04390-3 Installation And Owner's Manual

Air-cooled, prepackaged automatic standby generator 6 kw ng, 7 kw lp/12 kw ng, 12 kw lp/13 kw ng, 15 kw lp
Table of Contents

Advertisement

C
US
LISTED
Not intended for use as Primary Power in place of utility or in
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
Installation and
Owner's Manual
life-support applications.
DANGER
Air-cooled, Prepackaged
Automatic Standby Generators
Models:
04389-3 (6 kW NG, 7 kW LP)
04456-3 (12 kW NG, 12 kW LP)
04390-3 (13 kW NG, 15 kW LP)
GENERAC
POWER SYSTEMS, INC.
R
R

Advertisement

Table of Contents
loading

Summary of Contents for Generac Power Systems 04389-3, 04456-3, 04390-3

  • Page 1 LISTED  Not intended for use as Primary Power in place of utility or in DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY! Installation and Owner’s Manual Automatic Standby Generators life-support applications. DANGER Air-cooled, Prepackaged Models: 04389-3 (6 kW NG, 7 kW LP) 04456-3 (12 kW NG, 12 kW LP) 04390-3 (13 kW NG, 15 kW LP) GENERAC...
  • Page 2: Introduction

    INTRODUCTION Thank you for purchasing this model of the Guardian product line by Generac Power Systems Inc. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads dur- ing a utility power failure.
  • Page 3: Table Of Contents

    Introduction ...Inside Front Cover Read This Manual Thoroughly ... IFC Contents ... IFC Operation and Maintenance ... IFC How to Obtain Service ... IFC Authorized Dealer Locator Number ... IFC Safety Rules ...2 Standards Index ... 3 Section 1 – General Information ...4 Unpacking/Inspection ...
  • Page 4: Safety Rules

    IMPORTANT SAFETY INSTRUCTIONS Air-cooled 7 kW, 12 kW and 15 kW Generators  SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all opera- tors and potential operators of this equipment.
  • Page 5: Standards Index

     ELECTRICAL HAZARDS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion.
  • Page 6: Section 1 - General Information

    Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators DANGER  Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. UNPACKING/INSPECTION After unpacking, carefully inspect the contents for damage.
  • Page 7: The Generator

    THE GENERATOR Figure 1.1 – 7 kW, Single Cylinder GH-410 Engine Exhaust Enclosure Figure 1.2 – 12 kW and 15 kW, V-twin GT-990/760 Engine Exhaust Enclosure Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel Data...
  • Page 8: Specifications

    Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators SPECIFICATIONS 1.5.1 GENERATOR Rated Max. Continuous Power Capacity (Watts*) Rated Voltage Rated Max. Continuous Load Current (Amps) 120 Volts** 240 Volts Main Line Circuit Breaker Phase Number of Rotor Poles Rated AC Frequency Power Factor...
  • Page 9: System Set Led

    SYSTEM SET LED The “System Set” LED is lit when all of the following conditions are true: 1. The AUTO/OFF/MANUAL switch is set to the AUTO position. 2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense volt- age is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly.
  • Page 10: Location

    Section 1 — General Information Air-cooled 7 kW, 12 kW and 15 kW Generators 8. Refit the brass hose barb fitting to outlet port #1 and the square headed steel pipe plug to outlet port #2. 9. Reverse procedure steps 1-5 to reinstall demand regulator.
  • Page 11: Battery Installation

    1.10.2 TRANSFER SWITCH 1.10.2.1 7 kW, 12 kW and 15 kW Units The transfer switch shipped with this generator is enclosed in a NEMA 1 enclosure. This type of enclo- sure is intended for indoor use only. Follow these rules: •...
  • Page 12: Section 2 - Post Installation Start-Up And Adjustments

    Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators • Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water.
  • Page 13: Generator Tests Under Load

    7. When certain that utility supply voltage is compat- ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch. 8. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.
  • Page 14: Adjusting The Regulator (Natural Gas Only)

    Section 2 — Post Installation Start-up and Adjustments Air-cooled 7 kW, 12 kW and 15 kW Generators 5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker). 6.
  • Page 15: Engine Governor Adjustment

    If this procedure or the equipment are not available, locate the nearest Dealer and they can perform the adjustments. NOTE: A service fee may be charged for this adjustment. ENGINE GOVERNOR ADJUSTMENT If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows: 2.7.1 7 KW UNITS...
  • Page 16: Voltage Regulator Adjustment

    Section 3 — Operation Air-cooled 7 kW, 12 kW and 15 kW Generators 7. Restart the unit. 8. Slowly turn the idle adjust screw to adjust the no-load idle frequency to 63-63.5 Hz (with door open). 9. The governor is now set. 2.7.3 ADDITIONAL CORROSION PROTECTION...
  • Page 17: Automatic Transfer Operation

    3.2.2 “OFF” POSITION This switch position shuts down the engine. This position also prevents automatic operation. Figure 3.1 – Generator Control Panel EXTERNAL OUTLET FUSE GFCI CIRCUIT 7.5A BREAKER MAN. AUTO 12 VDC SYST EXERCISE ACCESSORY TIME OUTLET 7.5A MAX 3.2.3 “MANUAL”...
  • Page 18: Manual Transfer Operation

    Section 3 — Operation Air-cooled 7 kW, 12 kW and 15 kW Generators • If utility source voltage drops below about 60 percent of the nominal supply voltage, the sensor energizes a 15-second timer. • Once the timer has expired, the engine will crank and start.
  • Page 19: Setting The Exercise Timer

    5. Use the manual transfer handle inside the trans- fer switch to move the main contacts back to their UTILITY position, i.e., loads connected to the util- ity power source (Figure 3.2). 6. Turn ON the utility power supply to the transfer switch using the means provided.
  • Page 20: Section 4 - Maintenance

    Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators 3.7.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gen- erator from supplying an output that could poten- tially damage appliances connected to the generator circuit.
  • Page 21: Changing The Engine Oil

    CHANGING THE ENGINE OIL 4.3.1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil. Organic break-in oil is required before using synthetic oil. NOTE: The unit is supplied with “break-in” oil. See the “Break-in Procedure,”...
  • Page 22: Spark Plug(S)

    Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators Figure 4.7 — 12 kW and 15 kW Engine Air Cleaner Screw SPARK PLUG(S) Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See Section 4.13 for mainte- nance requirements.
  • Page 23: Adjusting

     Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed: • DO NOT SMOKE when near the battery; • DO NOT cause flame or spark in battery area; and • Discharge static electricity from body before touch- ing the battery by first touching a grounded metal surface.
  • Page 24: Attention After Submersion

    Section 4 — Maintenance Air-cooled 7 kW, 12 kW and 15 kW Generators  The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
  • Page 25: Service Schedule

    4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Authorized Dealer. SYSTEM/COMPONENT X = Action R = Replace as Necessary * = Notify Dealer if Repair is Needed. FUEL Fuel lines and connections* LUBRICATION Oil level Oil filter...
  • Page 26: Section 5 - Troubleshooting

    Section 5 — Troubleshooting Air-cooled 7 kW, 12 kW and 15 kW Generators TROUBLESHOOTING GUIDE Problem The engine will not crank. The engine cranks but will not start. The engine starts hard and runs rough. The Auto/Off/Manual switch is set to OFF , but the engine continues to run.
  • Page 27: Section 6 - Notes

    Section 6 — Notes Air-cooled 7 kW, 12 kW and 15 kW Generators...
  • Page 28 Section 6 — Notes Air-cooled 7 kW, 12 kW and 15 kW Generators...
  • Page 29 Section 6 — Notes Air-cooled 7 kW, 12 kW and 15 kW Generators...
  • Page 30: Section 7 - Electrical Data

    Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – V-Twin – Drawing No. 0E9016 DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - MAIN OUTPUT BREAKER CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PULL D - DIODE DSW - PCB MOUNTED DIP SWITCH...
  • Page 31 224A 225A 224A 224B 224B 225B 225B VOLTAGE REGULATOR 12VDC ACCESSORY SOCKET Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – V-Twin – Drawing No. 0E9016 CONTROL PANEL BOX 225A AUTO MANUAL Section 7 — Electrical Data CLOSEST TO BEARING EXTERNAL GFCI...
  • Page 32 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – V-Twin – Drawing No. 0E9017 C2-11 ELECTRONIC C2-10 VOLTAGE REGULATOR C2-8 (STATOR) DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - CIRCUIT BREAKER, MAIN OUTPUT CB2 - CIRCUIT BREAKER, ALT.
  • Page 33 225A 56VA 224A 12VDC ACCESSORY SOCKET C1-1 C1-5 Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – V-Twin – Drawing No. 0E9017 C2-6 C2-5 C2-1 BLACK CUSTOMER SUPPLIED Section 7 — Electrical Data 240VAC UTILITY INPUT 12Vdc TRANSFER RELAY COIL...
  • Page 34 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – Single Cylinder – Drawing No. 0E9014 DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - MAIN OUTPUT BREAKER CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PULL D - DIODE DSW - PCB MOUNTED DIP SWITCH...
  • Page 35 224A 225A 224A 224B 225B 224B VOLTAGE REGULATOR 12VDC ACCESSORY SOCKET Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – Single Cylinder – Drawing No. 0E9014 CONTROL PANEL BOX 225A 225B MANUAL Section 7 — Electrical Data CLOSEST TO BEA EXTERNAL GFCI...
  • Page 36 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – Single Cylinder – Drawing No. 0E9015 ELECTRONIC C2-10 VOLTAGE REGULATOR C2-8 DPE WINDING DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - CIRCUIT BREAKER, MAIN OUTPUT CB2 - CIRCUIT BREAKER, ALT.
  • Page 37 225A 56VA 224A 12VDC ACCESSORY SOCKET C1-1 C1-6 C1-5 Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – Single Cylinder – Drawing No. 0E9015 C2-6 C2-5 C1-2 BLACK CUSTOMER SUPPLIED Section 7 — Electrical Data 240VAC UTILITY INPUT 12Vdc TRANSFER...
  • Page 38 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 8 Circuit Load Center – Drawing No. 0E7687A...
  • Page 39 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 8 Circuit Load Center – Drawing No. 0E7687A...
  • Page 40 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 12 Circuit Load Center – Drawing No. 0E7687$...
  • Page 41 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 12 Circuit Load Center – Drawing No. 0E7687$...
  • Page 42 Section 7 — Electrical Data Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 8 Circuit Load Center – Drawing No. 0E7815A B E2 LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP...
  • Page 43 Electrical Schematic – 12 Circuit Load Center – Drawing No. 0E7815$ LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES Air-cooled 7 kW, 12 kW and 15 kW Generators NEUTRAL CONNECTION INSIDE SWITCH...
  • Page 44: Section 8 - Exploded Views And Parts Lists

    Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0F0080-C PRE PACKAGED UNITS ONLY...
  • Page 45 ITEM PART NO. QTY. DESCRIPTION 0C6140 ASSEMBLY, ENCLOSURE BASE 0D1901 ASSEMBLY, ENCLOSURE BASE (7KW) 0C6735 SUPPORT, ROOF FOLDING 0F0063 ENCLOSURE, FRONT 0C7062 ENCLOSURE, EXHAUST SIDE 0C7062A ENCLOSURE, EXHAUST SIDE (7KW) 0E8811 ENCLOSURE, SIDE & BACK 0E8811A ENCLOSURE, SIDE & BACK (7KW) 0E9873 ENCLOSURE, ROOF 0C7065...
  • Page 46 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0E9162-J...
  • Page 47 ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V (7KW) 0E7886E CIRCUIT BREAKER 50A X 2P 240V (12KW) 0E7886J CIRCUIT BREAKER 65A X 2P 240V (13/15KW) 0A1801 ASSEMBLY, BATTERY CHARGER ENGINE 083049 ASSEMBLY, POTTED REGULATOR 0C2174 RELAY, 12V 25A SPST 075210A BLOCK 1 POSITION 0D3062...
  • Page 48 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW, 8 Circuit Load Center Assembly – Drawing No. 0E7975-B...
  • Page 49 ITEM PART NO. 0D4801 0D4800 0C2237 077220 077220A 082574 084464 074908 024912 0A1658 063617 0E7889A 0A1495 0A1661 022473 0D3094 0D4684A 0E7900 0F4790 022152 064526 0E6155 063378 0A2110 074138 036933 077033 048850 028739 0D4802 0D3191 0D3088 073591 073590A 040213B 0E7888C 0A7215 0E7888B 0E7888A 0D3320...
  • Page 50 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW, 12 Circuit Load Center Assembly – Drawing No. 0E7973-F...
  • Page 51 12 kW and 15 kW, 12 Circuit Load Center Assembly – Drawing No. 0E7973-F ITEM PART NO. 0D3086 0D3092 0F5211 0C2237 077220 077220A 082574 084464 074908 024912 0A1658 063617 0E7889 0A1495 0A1661 022473 055450 025034 0D4684 0E7900 0F4790 022152 064526 0E6155 063378 0D3094...
  • Page 52 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Engine – Drawing No. 0E8774-M Part 1...
  • Page 53 ITEM PART NO. QTY. DESCRIPTION 0C5729 ASSEMBLY, CRANKCASE HOUSING WITH SLEEVE 0E9843 SEAL, 38 I.D. CRANKSHAFT 090388 SCREW, TAPTITE M6-1.0 X 12 YC 0C5372 ASSEMBLY, BREATHER 0C3005 GASKET, BREATHER COVER 0E3372B SEPARATOR, OIL BREATHER 0D8067A ASSEMBLY, HEAD #1 G&S 071983 RETAINER, PISTON PIN 20 0C2981C ROCKER, COVER NO OIL FILL...
  • Page 54 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Engine – Drawing No. 0E8774-M Part 2 97 98 123, 145...
  • Page 55 ITEM PART NO. QTY. DESCRIPTION 0C5136A KNOB, AIR CLEANER 0C3024 COVER, AIRBOX NG/LP 0C3040 PRE-CLEANER, 0C8127 ELEMENT, AIR CLEANER 0D8564A ASSEMBLY, MIXER/AIRBOX 990 0D8564B ASSEMBLY, MIXER/AIRBOX 760 0D2595 SCREW SHOULDER (8MM) M6-1.0 X 18 0D4417 WASHER,RUBBER 1/4" X 1/8" THICK 0C3025 SWITCH, OIL PRESS 0D3083...
  • Page 56 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW Generator – Drawing No. 0D3504-E...
  • Page 57 ITEM PART NO. 0C6934 0C9935H 0C9934H 0C6043A 0C8096 0C9593 0D3220 0C8860 031971 0C3168 056147 0D1847 0C7038C 0D1647 0D2558 0C7038B 0C7758 0388050AE0 0C2417A 082121C 066386 029451 049451 022237 022511 022131 039287 022145 049820 090388 022129 022259 059637 048031K 0C9592 048031M 040976 0C2824 025145 090239...
  • Page 58 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW Generator – Drawing No. 0D3417-L...
  • Page 59 ITEM PART NO. 0C6934 0C7930 0D2359 0C7944 0D2356 0C6043 0D2336 0D6634 0D3220 0C8101 056482 0C3168 0D1838 0D1846 0C7038 0D1609 0D2559 0C7038A 0C7758 0388050AD0 0C2417A 082121C 066386 029451 049451 022237 022511 022131 051731 022145 049820 045756 022129 022259 059637 0D4662 0F7065 048031M 0F0462 0C2824...
  • Page 60 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0F3981-A Part 1...
  • Page 61 ITEM PART NO. 0E3221 0E1466 021533 0E2985 071983 0E8440 0A7628 078658 078659 088261E 0E3812 0E6519 078645 0A7811 0A9877 076701 021713B 078691 0A5771 0A5776 076361 0A8898D 0D2274 0C4391 086025 0E3341 021714 086516 086517 0D9853B 083897 077158 0C3150 072694 083907 072696 078694 021742 0D6094 076329...
  • Page 62 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0F3981-A Part 2...
  • Page 63 ITEM PART NO. 0C1069 0D2922 0C8435 0C9997 088434 045756 0C4176A 0D9004A 059985 022129 0C2458A 083512 0D1401A 091039 0C9619 049811 022097 040945 086999 0D5667A 049821 099236 070185B 082774 091222E 067198N 067890 0E7585 072734 072735 0C3978 0C6040 0D9760 092079 0F3800 083502 082025 0D3083 0E7887C 090072...
  • Page 64 Section 8 — Exploded Views and Parts Lists Air-cooled 7 kW, 12 kW and 15 kW Generators Gas Regulator – Drawing No. 0D8720-H ITEM PART NO. QTY. DESCRIPTION 0D5694 CASTING, TWIN REGULATOR HOUSING 0F5022 SOLENOID COIL, 12VDC 0C4647 GASKET , SOLENOID 0D4166 PLUNGER, LP REGULATOR ASSEMBLY 0C6070...
  • Page 65: Section 9 - Mounting Dimensions

    Section 9 — Mounting Dimensions Air-cooled 7 kW, 12 kW and 15 kW Generators Drawing No. 0D3739-C CBHOM-F TYPE 120/240v CBHOM-F TYPE 120/240v CBHOM-F 120/240v TYPE CBHOM-F 120/240v TYPE CBHOM-F 120/240v TYPE 120/240v CBHOM-F TYPE TYPE HOM CBHOM-F CBHOM-F TYPE HOM TYPE HOM CBHOM-F TYPE HOM...
  • Page 66: Section 10 - Warranty

    Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
  • Page 67 Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
  • Page 68 "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Guardian generator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Guardian Authorized Warranty Service Dealer, is found to be defective.

Table of Contents