Initializing and Saving Data and Removing the Memory Card
1,2,3...
1,2,3...
Note
8-2-5

Initializing and Saving the Error Log

Initializing the Operation Log
1. Press the Initialize Button. A confirmation message will be displayed.
Press the Yes Button to initialize the data. Press the No Button to cancel
the initialize function.
2. When the Display Section has completed initializing the operation log, a di-
alog box will be displayed indicating that the operation log has finished be-
ing initialized.
Saving the Operation Log
1. Press the Save Button. The Save Button will be lit yellow while data is be-
ing saved.
2. When the Display Section has completed saving the operation log, the
Save Button will return to its normal color and a dialog box will be displayed
indicating that the save has been finished.
When saving the operation log, the operation log must be controlled from the
system memory. For details on controlling the operation log, refer to 2-4 Sys-
tem Memory in the NS-Series PT Programming Manual (V073).
This function initializes the macro error history saved in the NSJ Controller or
saves the history in the Memory Card.
Up to 100 errors can be recorded in the error log. The number of errors that
can be recorded, however, also depends on the free space in the memory.
The error log records the errors that occur when the macro function is exe-
cuted. Initialize or save the error history by using operations from the Initialize
Tab Page in the System Menu, as follows: