Wiring
Note
AI Series
AI 0.5-6WH: For thin cable power lines
AI 0.25-6BU: For thin cable signal lines
AI 0.5-10WH: For thin cable power lines
AI 0.25-8YE: For thin cable signal lines
AI 2.5-8BU: For thick cable
AI 2.5-12BU: For thick cable
AI Series
AI TWIN2 × 0.5-8WH (for thin cable)
H0.5/16.5 ZH
Note
96
4. Attach the crimp terminals (solderless pin terminals) to the lines and use
the proper Crimping Tool to crimp the terminal securely.
We recommend using the following crimp terminals and crimping tools.
Model
5. Cover the end of the cable with vinyl tape or heat-shrink tubing as shown
in the following diagram.
Vinyl tape or
heat-shrink tubing
6. Check that the connector is oriented correctly and the wire set screws are
loose enough to insert the wires. Insert the power lines, signal lines, and
shield wire in the correct holes in the following order (left to right): black,
blue, shield, white, and red.
(1) Be sure that the wire set screws are sufficiently loosened before attempt-
ing to insert the lines. If these screws are not loose, the wires will go into
the space in the back of the connector and cannot be locked with the set
screws.
(2) There are colored stickers provided on the connector and board that
match the colors of the lines to be inserted. Be sure that the colors match
when wiring the connectors.
Crimp terminal
Crimping tool
CRIMPFOX
For a single wire
UD6 or CRIMP-
FOX ZA3
For two wires
(multi-drop)
For two wires
(multi-drop)
Black (V−)
Blue (CAN L)
Shield
White (CAN H)
Red (V+)