Overview
Note
Note
Routing Tables for NSJ Controller 1
Local Network Table
Unit number
0 (built-in DeviceNet)
1 (NSJ Controller Link Unit)
228 (built-in Ethernet port)
Relay Network Table
Destination network
address
4
5
Network Address Setting for the Built-in Ethernet Port on the Display
Section of the NSJ Controller
The network address for the built-in Ethernet port is set using the communica-
tions settings on the Comm Tab Page on the System Menu of the Display
Section of the NSJ Controller. Set the network address to 1 (and set the IP
address and subnet mask). The address set here (1) is the same as the value
set in the local routing tables given above (228: built-in Ethernet port).
Set the same network address for the built-in Ethernet on the System Menu of
the Display Section and in the routing tables of the Controller Section.
Routing Tables for NSJ Controller 2
Local Network Table
Unit number
0 (built-in DeviceNet)
1 (NSJ Controller Link Unit)
Relay Network Table
Destination network
address
1
3
5
Routing Tables for NSJ Controller 3
Local Network Table
Unit number
0 (built-in DeviceNet)
1 (NSJ Controller Link Unit)
Relay Network Table
Destination network
address
1
3
4
(1) When routing tables are transferred to the NSJ Controller from a Pro-
gramming Device, the built-in DeviceNet Section, Expansion Unit, and
Display Section of the NSJ Controller will be reset to enable using the
Local network address
3
2
1
Relay network address
2
2
Local network address
4
2
Relay network address
2
2
2
Local network address
5
2
Relay network address
2
2
2
Section 1-1
Relay node address
2
3
Relay node address
1
1
3
Relay node address
1
1
2
17