Replacing the System Program
Manual Transfer
Use screen operations to select the direction (download or upload), contents (Project, Project & System, or
System), and banks.
Use one of the following procedures to manually transfer data.
1. Turn OFF the power to the NSJ Controller, turn ON pin 6 of the DIP switch, and turn ON the power to the
NSJ Controller.
DIP switch pin and status
1
2
3
OFF
OFF
OFF
2. Execute Memory Card Transfer from the Special Screen Tab Page of the System Menu. Refer to 11-1 Back-
up Function for details.
Use the following procedure to manually transfer data mentioned above in step 1.
1. Turn OFF the power to the NSJ Controller.
2. Turn ON pin 6 of the DIP switch.
3. Insert the Memory Card into the Display Section (MC (DISPLAY)).
4. Turn ON the power.
5. The following screen will be displayed on the Display Section.
6. Specify the direction, contents (project, project and system, or system), and bank.
7. The IPP file name and system version that are stored in both the specified bank of the Memory Card and
the Display Section will be displayed in the Project File and System Version fields. After confirming the de-
tails, press the Go Button.
8. A message confirming the transfer will be displayed. Press the OK Button to execute the specified data
transfer operation. When downloading, the screen data previously stored in the Display Section will be de-
leted.
9. A warning message will be displayed if the Display Section model, system program/screen data versions,
and language for the data stored in the Display Section are different from that for the data stored in the Mem-
ory Card. Press the Yes Button to continue transferring the data.
10. The uploading/downloading screen will be displayed while data is being transferred. A screen indicating that
the transfer has completed will be displayed when the transfer has finished. (If an error occurs, a transfer
error screen will be displayed. Refer to Errors on page 212 if an error occurs.)
11. The indicator will flash green when transferring has finished.
12. Turn OFF pin 6 of the DIP switch and reset the Display section.
The system settings cannot be changed for the upload operation (i.e., the system settings set with the CX-
Designer).
4
5
6
ON
Enables manually downloading or uploading the system program and
screen data.
OFF
OFF
Appendix A
Operation
211