Error Log Data - Omron SYSMAC CS1W-LCB01 Operation Manual

Loop control board
Hide thumbs Also See for SYSMAC CS1W-LCB01:
Table of Contents

Advertisement

Errors and Alarm Troubleshooting
LED Indicators
LED
on front of
Indicator on
Loop
front of CPU
Controller
Unit
RDY
EXEC
ERR/ALM
(See note.)
Not lit
Not lit
Lit
(A42400, the
Inner Board
WDT Error
Flag, is ON.)
Lit
(A42401, the
Inner Board
Bus Error
Flag, is ON.)
Lit
(A42403, the
Flash Mem-
ory Data Error
Flag, is ON.)
None of the
above
Flash-
Not lit
Lit
ing
Note
7-1-4

Error Log Data

228
Problem
Cause
An Inner
The Inner Board is mal-
Board
functioning.
WDT Error
occurred.
Inner
An Inner Board Bus
Board Bus
Error occurred.
Error
Parameter
One of the following
backup
problems was detected
data (flash
during a cold start with
memory)
the CS1W-LCB01/05 or
error
a cold or hot start with
the CS1D-CPU@@P.
1) The data was cor-
rupted by noise or other
factor.
2) The power was inter-
rupted during a backup.
(See note.)
3) The power was inter-
rupted during duplex ini-
tialization (CS1D-
CPU@@P only)
Note: If the function
block database (RAM) is
valid, the data will be
backed up when power
is turned ON again.
CPU Unit
A fatal error occurred in
Fatal Error
the CPU Unit.
CPU Unit
A CPU Unit WDT Error
WDT Error
occurred.
The CPU Unit's ALM/ERR Indicator will flash when a non-fatal error has
occurred and stay lit when a fatal error has occurred.
The configuration of error log data including error codes is as follows. Error
log data is stored in RAM (battery-backed up) on the Loop Controller. The
configuration of each error log is as follows and is regarded as a single record.
Error log data is not stored in flash memory.
RAM can hold up to 256 of the latest records:
1 record
Error code
Detailed information
Date (year/month) and time (hour/minute/second) of occurrence
Error log data can be read using the FINS (READ ERROR LOG, [command
code 2102 Hex]) command.
A record is not made in the error log if an error for which the error code is
already stored in flash memory.
Status
Error
code
(Stored in
error log.)
Operation is stopped
None
(fatal error.)
Operation is stopped
0014
(fatal error.)
Operation is stopped
0331
(fatal error.)
The details
code con-
tains either
the rele-
vant block
address or
FFFF if all
data bases
are invalid.
Operation is stopped
None
(fatal error.)
Operation is stopped
0001
(fatal error.)
Section 7-1
Corrective action
Turn the power OFF
and ON again. Replace
the Loop Control Board
if the error recurs when
the power is turned
ON.
Mount the Loop Con-
trol Board securely.
Replace the Loop Con-
trol Board if the error
recurs after the Board
is secured and power
is turned ON again.
Execute the Download
or Clear all operation
from CX-Process Tool
Version 3.0.
The Flash Memory
Data Error Flag
(A42403) will go OFF if
the data in RAM
becomes valid.
Refer to the CPU Unit's
Operation Manual and
clear the fatal error.
Refer to the CPU Unit's
Operation Manual.