Replacing the System Program
Errors
Errors during Automatic Transfer
The indicator on the front panel will flash red if an error occurs during data transfer.
Check the following items if an error occurs.
• Is the Memory Card inserted into the slot in the Display Section (MC (DISPLAY))?
• Do the banks set with the DIP switch exist in the Memory Card (during download)?
• Is the size of the transfer data greater than the free space in the Display Section or Memory Card?
Check these items before transferring data again.
Note An error message will not be displayed even if an error occurs.
Errors during Manual Transfer
If an error occurs during data transfer, a transfer error screen will be displayed. Check the following items for
the displayed message.
Error message
Memory Card Error
Could not recognize a Memory Card. Check the
Memory Card and reset the NS Hardware.
Project Transmission Error
Transmission Failed. Check the Memory Card
and reset the NS Hardware.
System Transmission Error
Transmission Failed. Check the Memory Card
and reset the NS Hardware.
Cannot find source data. Are you sure to continue
Downloading/Uploading?
After checking the message, reset the Display Section, and transfer the data again.
System Program Recovery/Update
It may not be possible to replace the system program using a normal download if the Display Section system
has been damaged, e.g., if the power was turned OFF while a file was being written. Use the following proce-
dure if system program replacement is not possible or the system program is damaged and the Display Section
does not start.
1. Copy Recover_6_5. to a Memory Card. This program can be installed with CX-Designer Ver. 1.01 by spec-
ifying it in the setup wizard.
2. Place the Memory Card into the slot in the Display Section (MC (DISPLAY)) and turn ON the power. The
recovery program will start automatically. Refer to the file How to recover Ver. 6_5.pdf for details on recovery
operations. This can be accessed from Windows Start - Programs - Omron - CX-One - CX-Designer -
How to recover the system prog Ver. 6.5.
3. The system will start automatically downloading data to the Display Section.
The indicator will flash green when the download has finished.
212
• Is the Memory Card inserted into the slot in the Display Section (MC
(DISPLAY))?
• Is the Memory Card damaged?
• Was the Memory Card removed during data transfer?
• Is there sufficient available space on the Memory Card?
• Is the Memory Card damaged?·
• Does the screen data volume exceed the memory capacity of the
Display Section?
• Does the transfer source directory or file exist?
(Note: If the Yes Button is pressed and data is transferred, the previ-
ous data at the transfer destination will be deleted.)