Figure 46. Normally Closed REPO Switch Wiring
REPO
Switch
(NC)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
Figure 47. Normally Closed and Normally Open REPO Switch Wiring
REPO
Switch
(NC)
REPO
Switch
(NO)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
T
NOTE
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
1
Twisted
Wires
2
Twisted
Wires
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)
UPS System Installation
85