Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Table 7. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395-
1100/750, and 9395-1100/825 – Common Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Each Battery Disconnect to
Each UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Pole
Units
kVA
kW
Volts
Amps
A
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Amps
B
AWG or kcmil
(each)
Total Amps
C
AWG or kcmil
(each)
Amps
D
AWG or kcmil
(each)
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Installation Plan and Unpacking
Rating 50/60 Hz
650
650
750
592
592
683
400/400 480/480 400/400 480/480 400/400 480/480
1070
892
1234
1029
500
500
500
(6)
(5)
(6)
782
1083
938
500
500
500
(5)
(5)
(5)
938
782
1083
500
500
500
(6)
(6)
(6)
1280
1503
1503
1280
500
500
500
(6)
(6)
(6)
782
1083
938
500
500
500
(5)
(5)
(5)
750
825
825
683
751
751
1358
1132
500
500
500
(5)
(6)
(5)
902
1191
992
500
500
500
(5)
(5)
(5)
902
1191
992
500
500
500
(6)
(6)
(6)
1600
1600
500
500
500
(6)
(6)
(6)
902
1191
992
500
500
500
(5)
(5)
(5)
31