UPS Maintenance

Figure 132. FI-UPM Air Filter Location

FI-UPM Air Filter
9 9 . . 2 2 . . 3 3 P P E E R R I I O O D D I I C C M M a a i i n n t t e e n n a a n n c c e e
Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit
evidence of overheating. Particular attention should be given to bolted connections. Maintenance procedures
should specify that the bolted connections be retorqued to values listed in this manual.
9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e
Annual preventive maintenance should be performed only by authorized service personnel familiar with
maintenance and servicing of the UPS system. Contact an Eaton service representative for more information
about service offerings.
9 9 . . 2 2 . . 5 5 B B A A T T T T E E R R Y Y M M a a i i n n t t e e n n a a n n c c e e
Contact an Eaton service representative for battery maintenance. Battery replacement and maintenance should
be performed only by authorized service personnel.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14