Eaton Power Xpert 9395 Installation And Operation Manual page 172

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

4.
On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode in approximately ten
seconds.
The ONLINE status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
7 7 . . 3 3 . . 1 1 4 4
S S t t a a r r t t V V a a r r i i a a b b l l e e M M o o d d u u l l e e M M a a n n a a g g e e m m e e n n t t S S y y s s t t e e m m H H i i g g h h A A l l e e r r t t M M o o d d e e f f r r o o m m t t h h e e B B y y p p a a s s s s C C o o m m m m a a n n d d M M e e n n u u
To start High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the BYPASS command.
3.
Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select START HIGH ALERT.
5.
Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying the critical load. After
one hour the UPS transfers to Variable Module Management System mode.
The ONLINE status indicator is illuminated. The UPS status indicates HIGH ALERT. The UPM status
indicates ONLINE. The power module is on.
7 7 . . 3 3 . . 1 1 5 5 S S t t a a r r t t i i n n g g t t h h e e U U P P M M s s
To start the power module without transferring the critical load to Online mode:
1.
Unfasten the front door latch and swing the door open (see
NOTE
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
2.
*Verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS Bypass input feeder circuit breaker.
5.
*Close input breaker CB1.
6.
Close the door and secure the latch.
7.
Observe the UPS control panel becoming active, indicating logic power.
8.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
9.
On the System Status screen, the UPS status should indicate SHUTDOWN and the UPM status should
indicate OFFLINE.
10. Verify no alarms are active.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Operating Instructions
Figure
17).
Figure
79).
151