Page 1
® ® Eaton Power Xpert 9395 High Performance (9395P-300) UPS Installation and Operation Manual For use with 380V, 400V, 415V, and 480V Single UPM (200–300 kVA), Plus 1 (400–600 kVA) UPS Models Also for use with 600V Single UPM (200–275 kVA), Two UPM (200–300 kVA),...
Page 3
® ® Eaton Power Xpert 9395 High Performance (9395P-300) UPS Installation and Operation Manual For use with 380V, 400V, 415V, and 480V Single UPM (200–300 kVA), Plus 1 (400–600 kVA) UPS Models Also for use with 600V Single UPM (200–275 kVA), Two UPM (200–300 kVA),...
Electrically Connecting the Sections (600V Models Only)........® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 6
Control Panel ..............® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 7
Building Alarm Monitoring ............. . . ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 8
WARRANTY ....................® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 9
Distributed Bypass System UPS CAN Wiring without MOBs........® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 11
FI-UPM Air Filter Location ............. . . ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 12
LIST OF FIGURES This page intentionally left blank. ® ® 1-viii Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
300 kVA. Adding the FI-UPM can also provide N+1 redundancy if the power requirements are less than the single UPM rating. The FI-UPM matches the UPS in style and color. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
ISBM Standard ISBM and 1 x UPM (380V, 400V, 415V, and 480V models) Figure 1-1. 415V/400V/380V and 480V Single UPM and Two UPM Configurations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS system. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection.
1.3.5 Power Management Software Intelligent Power Management and Intelligent Power Protector software are available through Eaton support. See Chapter 8, “Communication” for additional information. Options and Accessories Contact an Eaton sales representative for information about the following options.
1.4.8 Inherent Redundancy To deliver greater reliability, the 9395P-300 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM. Under normal conditions the UPMs in the UPS share the load equally.
X-Slot Cards – Optional X-Slot cards support several protocols, such as SNMP , HTTP , IBM AS/400, and Modbus. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
– PredictPulse is a subscription monitoring and ™ management service from Eaton that collects and analyzes data from connected power infrastructure devices, providing us with the insight needed to make recommendations and take action on your behalf. It’s also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of...
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system – the UPS cabinet, the battery system, and options or accessories installed. ® ® 1-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Mechanical installation instructions, including site preparation, planning for mechanical installation, and safety information. Detailed illustrations of the cabinet, including dimension and pallet removal drawings. Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain copies of these manuals. ®...
Call your local service representative Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual: E-ESSDocumentation@eaton.com ® ® 1-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
(ground) connection with loads attached. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 26
Keep surroundings uncluttered, clean, and free from excess moisture. Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 27
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 28
Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If the UPS is to be operated at an altitude higher than 1000m (3300 ft), contact an Eaton service representative for important information about high altitude operation. The operating environment must meet the weight, clearance, and environmental requirements specified.
Allow clearance in front of and above each cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2. Dimensions are in millimeters (inches). ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 33
Recommended Operating Range: 20–25°C (68–77°F) Maximum Relative Humidity: 95%, non-condensing NOTE Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supersede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty.
Page 34
225 kW Eaton 9395P-300/200 200 kVA 600/600 11.1 (37.73) (CSS or IOM) 200 kW NOTE CSS = Continuous Static Switch; IOM = Input Output Module ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Installed FI-UPM (shipped separately to be added to configuration later). See Figure 3-2. Two UPM: ISBM and 2 x UPM section (shipped joined on a single pallet). See Figure 3-3. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Standard ISBM and 1 x UPM with 1 Field Installed UPM (380V, 400V, 415V, and 480V models) Dimensions are in millimeters [inches]. Figure 3-2. Single UPM Configuration, Plus 1 FI-UPM (Dimensions) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
1873.9 [73.8] [29.3] Front View 600V ISBM Section with 1 x UPM Section Dimensions are in millimeters [inches]. Figure 3-4. 600V Single UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
600V ISBM Section with 1 x UPM Section and Upgraded with 1 Field Installed UPM Dimensions are in millimeters [inches]. Figure 3-5. 600V Single UPM Configuration, Plus 1 FI-UPM ® ® 3-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
[73.8] [52.4] Front View 600V ISBM Section with 2 x UPM Section Dimensions are in millimeters [inches]. Figure 3-6. 600V Two UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-11...
Measurements 918.0 [36.1] Dimensions are in millimeters [inches]. NOT INTENDED FOR PERMANENT MOUNTING Figure 3-7. Side View Dimensions and Center of Gravity Measurements ® ® 3-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
(from a Wye source) for proper equipment operation. The Eaton 9395P-300 480V and 600V unit is designed for operation on a grounded-wye source of supply. There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads.
Page 44
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 45
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 46
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 47
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 48
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 49
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 50
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 51
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 52
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 53
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 54
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 55
Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
Page 56
Output UPM AC Input, UPM Battery Input, UPM AC Conical Washer 180500037-080 Output UPM AC Input, UPM Battery Input, UPM AC 180200001-05 Output ® ® 3-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 57
Rectifier Input, Bypass Input, Conical Washer 180500037-120 Battery Input, and Output Rectifier Input, Bypass Input, 180200001-07 Battery Input, and Output Table 3-21. Recommended Installation Parts and Tools (Not Supplied by Eaton) Part Size Quantity Manufacturer Part Number Notes 2/0 AWG Thomas &...
Page 58
Bypass conduit data is not applicable to IOM configurations. Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-6 to 3-7 Input/Output Ratings and External Wiring Requirements. ® ® 3-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 59
Bypass conduit data is not applicable to IOM configurations. Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-10 to 3-11 Input/Output Ratings and External Wiring Requirements ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-29...
Page 60
100% and 80% breaker ratings for rectifier input. NOTE For the 9395P-300 400/415/380V models, the max output is 300 kW/ 300 kVA. ® ® 3-30 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG. The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-33...
The UPS cabinet is palletted separately for shipping. The cabinet is shipped bolted to a wooden pallet and protected with outer protective packaging material. ® ® 3-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 65
Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-35...
Page 66
UPS Installation Plan and Unpacking Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement.
UPS Installation Plan and Unpacking Figure 3-8. Single UPM Configuration as Shipped on Pallet (380V, 400V, 415V, and 480V) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-37...
UPS Installation Plan and Unpacking Figure 3-9. Two UPM Configuration as Shipped on Pallet (380V, 400V, 415V, and 480V) ® ® 3-38 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
éviter de renverser les armoires, ce qui pourrait causer de graves blessures. CAUTION Do not tilt cabinets more than 10° from vertical. Lift the cabinets only with a forklift or damage may occur. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 70
(see Table 3-1 for cabinet weight). NOTE If an FI-UPM is ordered later, use the Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503) for installation instructions. The FI-UPM is always installed on the side opposite the factory-installed UPMs. See Figure 1-1.
This figure depicts the Shipping Bracket on the 380V, 400V, 415V, and 480V Two UPM configuration pallet. The 600V sections are oriented the same way and the shipping brackets are removed the same way as this illustration. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If installing an FI-UPM, go to paragraph 4-5. If installing a battery system, go to paragraph 4-6. Otherwise, go to paragraph 4-7 to complete the wiring of the UPS. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Remove the screws securing the left middle panel and remove the panel (see Figure 4-3). Retain the hardware for later use. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
UPM Section Base ISBM Section Base Front View Base Bracket Screw from Kit Screw from Kit Figure 4-5. ISBM Section to UPM Section Joining Brackets ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If necessary, loosen the screws securing the protective cage. Locate the mating P50 connector in the UPM section wireway and connect the P50 connector to the J50 connector. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7; otherwise, proceed to paragraph 4.8. DC Power Terminals Figure 4-7. 600V ISBM Section Intercabinet DC Power Terminal Locations ® ® 4-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Figure 4-9. J39 Location on Pl1 Interface Board Field Installed UPM Installation If installing a Plus 1 configuration with an FI-UPM, install the FI-UPM using the instructions in the Eaton® Power Xpert® 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503). After the FI-UPM is installed, proceed to paragraph 4.6 in this document if installing a battery system;...
Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) BOTTOM VIEW Figure 4-12. ISBM and UPM Section Conduit and Wire Entry Locations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-15...
Page 84
C power wiring from output terminals to the critical load. See paragraph 3.2.5 for wiring and termination requirements. 12. Proceed to paragraph 4.8.3. ® ® 4-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Se reporter au chapitre 10 sur les notices techniques pour connaître les tensions maximales du chargeur de batteries.Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement. To install wiring to connections:...
Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. AVERTISSEMENT! Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur n’est pas totalement débranché. ® ® 4-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-23...
NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG. Figure 4-20. Typical Alarm Relay Connection ® ® 4-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4-21. Terminal Blocks TB1, TB2, and TB3 Connector Assignments ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-27...
11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. If wiring X-Slot connections, proceed to paragraph 4.9.3; otherwise, proceed to Step 13. 13. Close the door and secure the latch. ® ® 4-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4-23. Typical Battery Interface Connection – Separate Battery System ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-29...
When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). To install wiring to connections: If not already installed, install the LAN drops.
The REPO switch must be a normally-open or normally-closed latching-type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
Figure 4-28 shows the wiring connections if the normally-closed REPO contacts are used and Figure 4-29 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-33...
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4-29. Normally-Closed and Normally-Open REPO Switch Wiring ® ® 4-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) The debris shields covering the UPS cabinet ventilation grills are removed. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. ®...
Controller Area Network (CAN) wiring between the UPS cabinets is properly installed. Pull-chain wiring between the UPS cabinets is properly installed. Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. ® ®...
Page 106
Distributed Bypass Installation Checklist This page intentionally left blank. ® ® 4-38 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Hot Sync CAN Bridge card (see paragraph 5.1) Parallel system wiring (see paragraph 5.2) RMP II (see paragraph 5.3) RIM II (see paragraph 5.4) SCM II (see paragraph 5.5) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Figure 4-18 and Figure 4-24 for X-Slot communication bay locations. To locate the appropriate terminals on the Hot Sync CAN Bridge Card, see Figure 5-2 and Table 5-1. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Normally-open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN input for parallel operation. Shield ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
NOTE Setup of the Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the top internal safety shield panel and secure with the retained hardware.
NOTE Use twisted pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5-6. Distributed Bypass Pull-Chain Wiring with MOBs ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Remove the ISBM cabinet top right interface conduit landing plate to drill or punch conduit holes (see Figure 4-12). Reinstall the conduit landing plate. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Terminal TB1 Signal Connections from the UPS Terminal TB3 120 Vac Power Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If all connections are secure but the RMP II continues to self-test, replace the fuse with the spare included in the hardware kit. If a fuse replacement does not correct the problem, contact an Eaton service representative for verification that the RMP II is working correctly.
Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior to making connections with J1 through J4 (see Table 5-6 and Figure 5-9).
Install 120 Vac power wiring from the critical bus to the SCM II. See Figure 5-10, Figure 5-8, and Table 5-5 for the terminal location and wiring information. ® ® 5-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Connections from the UPS Figure 5-10. Supervisory Contact Module II Terminal Location NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
Accessory Mounting Dimensions Figure 5-12 through Figure 5-14 show the dimensions of the RMP II, the RIM II, and the SCM II. ® ® 5-14 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-12. Remote Monitor Panel II Dimensions ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 5-15...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-13. Relay Interface Module II Dimensions ® ® 5-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-14. Supervisory Contact Module II Dimensions ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 5-17...
Page 124
Installing Options and Accessories This page intentionally left blank. ® ® 5-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Chapter 6 Understanding UPS Operation UPS System Overview The Eaton Power Xpert 9395P-300 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
DC voltage charge current to the battery. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
(customer configurable). At the completion of the hour, the UPS defaults back to VMMS mode. If the High Alert command is received during the one hour, the one hour timer will be restarted. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
K3 opens to isolate the inverter. The backfeed protection contactor is normally closed, ready to support the static switch unless the bypass input source becomes unavailable ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
DC voltage level is reached where the inverter output can no longer support the shared loads. If the bypass source is available, the UPS transfers to bypass instead of shutting down. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Figure 6-4. Path of Current Through the UPS in Battery Mode ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. , and Figure 6-13. Two UPM, Common Rectifier Feed, Common Battery, IOM Configuration ® ® 6-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Tables 3-7, 3-9, 3-11, 3-13, 3-15 or 3-17. , and Figure 6-14. Two UPM, Common Rectifier Feed, Separate Battery, IOM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-19...
(BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6-15. Simplified Dual-Feed UPS with Maintenance Bypass Panel ® ® 6-20 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The UPSs switch operating modes in response to these system events: ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-21...
Closed Output to Main Power Flow Critical Load Open Figure 6-16. Path of Current through the UPSs in Online Mode - Distributed Bypass ® ® 6-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Closed Output to Main Power Flow Critical Load Open Figure 6-17. Path of Current through the UPSs in Bypass Mode - Distributed Bypass ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-23...
When this event occurs, the system shuts down. If the bypass source is available, the system transfers to bypass instead of shutting down. ® ® 6-24 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 7.3. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
A horizontal row of LED indicators (2) Before system power up, the panel displays a system status screen similar to the one shown in Figure 7-2. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right corner of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password request pop-up (see Figure 7-4). ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
Yellow lines indicates an out-of-tolerance condition. NOTE Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Figure 7-6. Main Menu and Power Maps Screen (Online Mode) Touching the LOAD kVA button displays the Output kVA screen shown in Figure 7-7. Figure 7-7. Output kVA Screen from Home Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Figure 7-8. Average Efficiency Screen from Home Screen Touching the CONSUMPTION button displays the screen shown in Figure 7-9. Figure 7-9. Consumption Screen from Home Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Figure 7-11 is an example of a command request confirmation pop-up screen. This type of pop-up allows the user to confirm that the requested command is valid. Figure 7-11. Typical Command Confirmation Screen (Charger Off) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
24 hours, 7 days, 30 days, or 1 year. This is true of all the meters screens listed in the top section. Figure 7‐8 Figure 7‐9 Figure 7-12. Meters Summary Screen ® ® 7-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The Select Source screen shown in Figure 7-17allows the operator to choose the individual source for system readings. Figure 7-17. Select Source Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-13...
This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. ® ® 7-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Selecting an event opens the Event Detail screen shown in Figure 7-24. This screen details the specifics of the event for the user to see. Figure 7-24. User Log Detail Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-17...
Figure 7-26 shows the Module Controls screen. This screen allows control of the individual modules within the system. It also gives their values and status. Figure 7-26. Module Controls Screen ® ® 7-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Figure 7-30. Settings Screen ® ® 7-20 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The various Energy Advantage Architecture operations are described in the UPS Installation and Operation manual for your system. Figure 7-32. Energy Advantage Architecture (EAA) Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-21...
Figure 7-34. High Alert Timer Screen This screen shown in Figure 7-34 asks the operator if they want to start the High Alert mode timer. ® ® 7-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The screen shown in Figure 7-35 allows the operator to query the system for various operational statistics such as shown in Figure 7-36. Figure 7-35. Statistics Basic Screen Figure 7-36. Statistics Data Detail Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-23...
UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. ® ® 7-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
L ’intérieur de l’armoire de l’onduleur est alimenté jusqu’à ce que le disjoncteur du circuit d’alimentation en amont soit activé. Activated Deactivated Pushbutton locked into place Unlock pushbutton to release Figure 7-40. REPO Operation ® ® 7-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The UPM status indicates ONLINE, CHARGING on the MIMIC Screen. 17 . To activate, enable, or disable any of the UPS operational modes, follow the online screen prompts. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-29...
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, the UPS status should indicate SHUTDOWN and the UPM status should indicate OFFLINE. ® ® 7-30 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the UPM command. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-31...
The input, output, battery, and bypass backfeed contactors open, and the power module is turned off on the UPS being shut down. Logic power remains on. ® ® 7-32 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
UPMs are shut down. 12. Perform the LOAD OFF procedure in paragraph 7.5.11 or paragraph 7.5.12 on the UPS being shut down. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-33...
13. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is displayed. 14. On the UPS Control Command screen, select GO TO ONLINE. ® ® 7-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
On the Charger Control Command screen, select CHARGER ON. Press the SELECT pushbutton on the Charger Command menu bar. To turn off the battery charger: ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-35...
Restart the UPS after pressing the LOAD OFF pushbutton by following the procedure in paragraph 7.5.1 or 7.5.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. ® ® 7-36 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Restart the UPS by following the procedure in paragraph 7.5.1 or 7.5.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-37...
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to the manual supplied with the X-Slot card for user instructions.
Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
Management Software for UPS management and monitoring, and Eaton LanSafe software, which allows graceful shutdown of operating systems. Eaton’s Intelligent Power Software gives you all the tools you need to monitor and manage power devices on your network, even in a virtualized environment. This innovative software solution combines the most critical applications in ensuring system uptime and data integrity: not only power monitoring and management, but also graceful shutdown during an extended power outage.
The RMP II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-2 shows an RMP II. Figure 8-2. Remote Monitor Panel II ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 199
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
BATTERY WEAK Pins 5 and 14 critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
BYPASS NOT AVAILABLE TB2-10 through TB2-12 ON BATTERY TB2-13 through TB2-15 UPS ALARM TB2-16 through TB2-18 ON BYPASS TB2-19 through TB2-21 SHUTDOWN IMMINENT TB2-22 through TB2-24 ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Page 202
Communication This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative.
Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See Figure 9-1 and Figure 9-2 for filter locations, and Table 9-1 for filter sizes. Contact an Eaton service representative for replacement filters. To remove and replace the filters: Table 9-1.
If the UPS configuration included an FI-UPM model, check the FI-UPM air filter (located behind the front panel) and wash or replace as necessary. See Figure 9-2 for the filter location. The FI-UPM filter size is 20” X 44” X 0.25” . Contact an Eaton service representative for a replacement filter. To remove the filter: ®...
UPS Maintenance ® Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton ® Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)). Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
9.2.4 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 9.2.5 BATTERY Maintenance Contact an Eaton service representative for battery maintenance.
Ne pas éliminer les déchets d’équipements électriques et électroniques (DEEE) aux ordures. Pour connaître la méthode d’élimination appropriée, communiquer avec le centre régional de récupération/réutilisation ou d’élimination des déchets dangereux. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
UPS Maintenance Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk (see page 1-10).
Page 210
UPS Maintenance This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
The UPS is housed in one or two free-standing cabinets with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings. Power Models Rating Frequency Eaton 9395P-300/300 (one or two UPM) 300 kVA, 50/60 Hz 300 kW Eaton 9395P-300/275 (one or two UPM) 275 kVA,...
.7 Hz per second maximum Load Compatibility 0.9 pF Leading 0.7 pF Lagging Overload Capability 110% for 10 minutes 125% for 120 seconds 150% for 15 seconds ® ® 10-2 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without Immunity damage and with no disturbance or adverse effect to the critical load. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 10-3...
Page 214
Product Specifications This page intentionally left blank. ® ® 10-4 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
Eaton-built battery cabinets, (individually and collectively, the “Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts and labor, as applicable), at the option of Eaton.
Page 216
Warranty This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...