9395 High Performance (9395P-300) UPS
Installation and Operation Manual
For use with 380V, 400V, 415V, and 480V Single UPM (200–300 kVA), Plus 1 (400–600 kVA) UPS Models
Also for use with 600V Single UPM (200–275 kVA), Two UPM (200–300 kVA),
and Plus 1 (200–300 kVA)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Power Xpert 9395 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton Power Xpert 9395

  • Page 1 ® ® Eaton Power Xpert 9395 High Performance (9395P-300) UPS Installation and Operation Manual For use with 380V, 400V, 415V, and 480V Single UPM (200–300 kVA), Plus 1 (400–600 kVA) UPS Models Also for use with 600V Single UPM (200–275 kVA), Two UPM (200–300 kVA),...
  • Page 3 ® ® Eaton Power Xpert 9395 High Performance (9395P-300) UPS Installation and Operation Manual For use with 380V, 400V, 415V, and 480V Single UPM (200–300 kVA), Plus 1 (400–600 kVA) UPS Models Also for use with 600V Single UPM (200–275 kVA), Two UPM (200–300 kVA),...
  • Page 4 National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All other trademarks are property of their respective companies. ©Copyright 2018 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 5: Table Of Contents

    Electrically Connecting the Sections (600V Models Only)........® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 6 Control Panel ..............® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 7 Building Alarm Monitoring ............. . . ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 8 WARRANTY ....................® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 9 Distributed Bypass System UPS CAN Wiring without MOBs........® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 10 Figure 7-15. Output Meters Screen ..............7-12 ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 11 FI-UPM Air Filter Location ............. . . ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 12 LIST OF FIGURES This page intentionally left blank. ® ® 1-viii Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 13: Introduction

    300 kVA. Adding the FI-UPM can also provide N+1 redundancy if the power requirements are less than the single UPM rating. The FI-UPM matches the UPS in style and color. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 14: Single Upm And Two Upm Configurations

    ISBM Standard ISBM and 1 x UPM (380V, 400V, 415V, and 480V models) Figure 1-1. 415V/400V/380V and 480V Single UPM and Two UPM Configurations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 15: Figure 1-2. 600V 2X Upm Configuration

    Introduction 2x UPM ISBM 600V 300kW UPS ISBM and 2 x UPMs Figure 1-2. 600V 2x UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 16: Single Upm Plus 1 Upm Configuration

    Field Upgraded PLUS 1 UPM UPS with 1 UPM + 1 FI-UPM (380V, 400V, 415V, and 480V) Figure 1-3. Single UPM Plus 1 UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 17: Ups Standard Features

    Customer Service Engineer, or the warranty terms specified on page W-1 become void. This service is offered as part of the sales contract for the UPS system. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection.
  • Page 18: Advanced Battery Management

    1.3.5 Power Management Software Intelligent Power Management and Intelligent Power Protector software are available through Eaton support. See Chapter 8, “Communication” for additional information. Options and Accessories Contact an Eaton sales representative for information about the following options.
  • Page 19: Distributed Bypass System

    1.4.8 Inherent Redundancy To deliver greater reliability, the 9395P-300 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy. When configured, the UPS automatically becomes redundant if the load is at or below the capacity of the UPMs minus the capacity of one UPM. Under normal conditions the UPMs in the UPS share the load equally.
  • Page 20: Energy Saver And High Alert Modes

    X-Slot Cards – Optional X-Slot cards support several protocols, such as SNMP , HTTP , IBM AS/400, and Modbus. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 21: Battery System

    – PredictPulse is a subscription monitoring and ™ management service from Eaton that collects and analyzes data from connected power infrastructure devices, providing us with the insight needed to make recommendations and take action on your behalf. It’s also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of...
  • Page 22: Using This Manual

    In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system refers to the entire power protection system – the UPS cabinet, the battery system, and options or accessories installed. ® ® 1-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 23: Symbols, Controls, And Indicators

    Mechanical installation instructions, including site preparation, planning for mechanical installation, and safety information. Detailed illustrations of the cabinet, including dimension and pallet removal drawings. Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain copies of these manuals. ®...
  • Page 24: Getting Help

    Call your local service representative Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual: E-ESSDocumentation@eaton.com ® ® 1-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 25: Safety Warnings

    (ground) connection with loads attached. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 26 Keep surroundings uncluttered, clean, and free from excess moisture. Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 27 End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 28 Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 29 Section I Installation...
  • Page 31: Ups Installation Plan And Unpacking

    If the UPS is to be operated at an altitude higher than 1000m (3300 ft), contact an Eaton service representative for important information about high altitude operation. The operating environment must meet the weight, clearance, and environmental requirements specified.
  • Page 32: Installation Considerations

    Allow clearance in front of and above each cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-2. Dimensions are in millimeters (inches). ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 33 Recommended Operating Range: 20–25°C (68–77°F) Maximum Relative Humidity: 95%, non-condensing NOTE Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental requirements supersede the UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty.
  • Page 34 225 kW Eaton 9395P-300/200 200 kVA 600/600 11.1 (37.73) (CSS or IOM) 200 kW NOTE CSS = Continuous Static Switch; IOM = Input Output Module ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 35: 380V, 400V, 415V, And 480V Model Configurations

    Installed FI-UPM (shipped separately to be added to configuration later). See Figure 3-2. Two UPM: ISBM and 2 x UPM section (shipped joined on a single pallet). See Figure 3-3. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 36: Figure 3-1. Single Upm Configuration Dimensions

    ISBM with 1 Factory Installed UPM (380V, 400V, 415V, and 480V models) 871.5 [34.3] 1880 Side View [74.0] Figure 3-1. Single UPM Configuration Dimensions ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 37: Figure 3-2. Single Upm Configuration, Plus 1 Fi-Upm (Dimensions)

    Standard ISBM and 1 x UPM with 1 Field Installed UPM (380V, 400V, 415V, and 480V models) Dimensions are in millimeters [inches]. Figure 3-2. Single UPM Configuration, Plus 1 FI-UPM (Dimensions) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 38: Figure 3-3. Two Upm Configuration (Dimensions)

    ISBM with 2 Factory Installed UPMs (380V, 400V, 415V, and 480V models) 871.5 [34.3] 1880 Side View [74.0] Dimensions are in millimeters [inches]. Figure 3-3. Two UPM Configuration (Dimensions) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 39: 600V Model Configurations

    1873.9 [73.8] [29.3] Front View 600V ISBM Section with 1 x UPM Section Dimensions are in millimeters [inches]. Figure 3-4. 600V Single UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 40: Figure 3-5. 600V Single Upm Configuration, Plus 1 Fi-Upm

    600V ISBM Section with 1 x UPM Section and Upgraded with 1 Field Installed UPM Dimensions are in millimeters [inches]. Figure 3-5. 600V Single UPM Configuration, Plus 1 FI-UPM ® ® 3-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 41: Figure 3-6. 600V Two Upm Configuration

    [73.8] [52.4] Front View 600V ISBM Section with 2 x UPM Section Dimensions are in millimeters [inches]. Figure 3-6. 600V Two UPM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-11...
  • Page 42: Figure 3-7. Side View Dimensions And Center Of Gravity Measurements

    Measurements 918.0 [36.1] Dimensions are in millimeters [inches]. NOT INTENDED FOR PERMANENT MOUNTING Figure 3-7. Side View Dimensions and Center of Gravity Measurements ® ® 3-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 43: Ups System Power Wiring Preparation

    (from a Wye source) for proper equipment operation. The Eaton 9395P-300 480V and 600V unit is designed for operation on a grounded-wye source of supply. There is no additional connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral loads.
  • Page 44 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 45 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 46 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 47 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 48 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 49 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 50 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 51 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 52 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 53 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 54 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 55 Figure 6-5 on page 10 through Figure 6-14 on page 19. NOTE Bypass wiring data is not applicable to IOM configurations. Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system performance and battery run time. Battery Cable Routing Requirements Conduit applications: * Each conduit must have a Positive, Negative, and Ground conductor.
  • Page 56 Output UPM AC Input, UPM Battery Input, UPM AC Conical Washer 180500037-080 Output UPM AC Input, UPM Battery Input, UPM AC 180200001-05 Output ® ® 3-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 57 Rectifier Input, Bypass Input, Conical Washer 180500037-120 Battery Input, and Output Rectifier Input, Bypass Input, 180200001-07 Battery Input, and Output Table 3-21. Recommended Installation Parts and Tools (Not Supplied by Eaton) Part Size Quantity Manufacturer Part Number Notes 2/0 AWG Thomas &...
  • Page 58 Bypass conduit data is not applicable to IOM configurations. Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-6 to 3-7 Input/Output Ratings and External Wiring Requirements. ® ® 3-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 59 Bypass conduit data is not applicable to IOM configurations. Battery Conductor Routing: Refer to the notes at the bottom of Tables 3-10 to 3-11 Input/Output Ratings and External Wiring Requirements ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-29...
  • Page 60 100% and 80% breaker ratings for rectifier input. NOTE For the 9395P-300 400/415/380V models, the max output is 300 kW/ 300 kVA. ® ® 3-30 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 61 450A Eaton 9395P-600/275 350A 350A 450A 500A 500A 600A 250A 300A 350A 350A 400A 400A Eaton 9395P-600/250 350A 350A 400A 450A 500A 500A ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-31...
  • Page 62 All Ratings Eaton 9395P-300/300 800A Eaton 9395P-300/275 Eaton 9395P-300/250 700A Eaton 9395P-300/225 Eaton 9395P-300/200 NOTE Bypass conduit data is not applicable to IOM configurations ® ® 3-32 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 63: Ups System Interface Wiring Preparation

    REPO wiring should be a minimum of 22 AWG and a maximum of 14 AWG. The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-33...
  • Page 64: Distributed Bypass Power Wiring Preparation

    The UPS cabinet is palletted separately for shipping. The cabinet is shipped bolted to a wooden pallet and protected with outer protective packaging material. ® ® 3-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 65 Si ces instructions ne sont pas suivies, des dommages au câblage et à son canal surviendront. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-35...
  • Page 66 UPS Installation Plan and Unpacking Carefully inspect the outer packaging for evidence of damage during transit. CAUTION Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately. ATTENTION! Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement.
  • Page 67: Figure 3-8. Single Upm Configuration As Shipped On Pallet (380V, 400V, 415V, And 480V)

    UPS Installation Plan and Unpacking Figure 3-8. Single UPM Configuration as Shipped on Pallet (380V, 400V, 415V, and 480V) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 3-37...
  • Page 68: Figure 3-9. Two Upm Configuration As Shipped On Pallet (380V, 400V, 415V, And 480V)

    UPS Installation Plan and Unpacking Figure 3-9. Two UPM Configuration as Shipped on Pallet (380V, 400V, 415V, and 480V) ® ® 3-38 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 69: Installation

    éviter de renverser les armoires, ce qui pourrait causer de graves blessures. CAUTION Do not tilt cabinets more than 10° from vertical. Lift the cabinets only with a forklift or damage may occur. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 70 (see Table 3-1 for cabinet weight). NOTE If an FI-UPM is ordered later, use the Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503) for installation instructions. The FI-UPM is always installed on the side opposite the factory-installed UPMs. See Figure 1-1.
  • Page 71: Figure 4-1. Removing The Isbm Section Left Side Shipping Bracket

    This figure depicts the Shipping Bracket on the 380V, 400V, 415V, and 480V Two UPM configuration pallet. The 600V sections are oriented the same way and the shipping brackets are removed the same way as this illustration. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 72: Figure 4-2. Removing The Isbm Section Right Side Shipping Bracket

    If installing an FI-UPM, go to paragraph 4-5. If installing a battery system, go to paragraph 4-6. Otherwise, go to paragraph 4-7 to complete the wiring of the UPS. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 73: Mechanically Joining The Sections (600V Models Only)

    Remove the screws securing the left middle panel and remove the panel (see Figure 4-3). Retain the hardware for later use. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 74: Figure 4-4. Isbm And Upm Sections Joined

    Tie Wrap Locations Output Autotransformer T2 UPM Wireway Input Autotransformer T1 (Power wiring harnesses are coiled in this area.) Figure 4-4. ISBM and UPM Sections Joined ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 75: Figure 4-5. Isbm Section To Upm Section Joining Brackets

    UPM Section Base ISBM Section Base Front View Base Bracket Screw from Kit Screw from Kit Figure 4-5. ISBM Section to UPM Section Joining Brackets ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 76: Electrically Connecting The Sections (600V Models Only)

    If necessary, loosen the screws securing the protective cage. Locate the mating P50 connector in the UPM section wireway and connect the P50 connector to the J50 connector. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 77: Figure 4-6. Ups Intercabinet Interface Harness Locations

    Output Autotransformer T2 Input Autotransformer T1 ISBM Section Right Side View UPM Section Left Side View Figure 4-6. UPS Intercabinet Interface Harness Locations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 78: Connecting Intercabinet Can Cables And Connectors

    If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7; otherwise, proceed to paragraph 4.8. DC Power Terminals Figure 4-7. 600V ISBM Section Intercabinet DC Power Terminal Locations ® ® 4-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 79: Figure 4-8. Pl1 Interface Board Location

    Installation Pl1 Interface Board Front Figure 4-8. Pl1 Interface Board Location ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-11...
  • Page 80: Field Installed Upm Installation

    Figure 4-9. J39 Location on Pl1 Interface Board Field Installed UPM Installation If installing a Plus 1 configuration with an FI-UPM, install the FI-UPM using the instructions in the Eaton® Power Xpert® 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503). After the FI-UPM is installed, proceed to paragraph 4.6 in this document if installing a battery system;...
  • Page 81: Installing Ups External And Battery Power Wiring

    Flat Washer Bolt Head Cable Connection Bolt Orientation Double Lug Installation Figure 4-10. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-13...
  • Page 82: External Power Wiring Installation

    UPM Ventilation Grill Debris Shield (Remove shield before operating system.) TOP VIEW Front UPM Front ISBM Figure 4-11. ISBM and UPM Section Debris Shields ® ® 4-14 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 83: Figure 4-12. Isbm And Upm Section Conduit And Wire Entry Locations

    Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) BOTTOM VIEW Figure 4-12. ISBM and UPM Section Conduit and Wire Entry Locations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-15...
  • Page 84 C power wiring from output terminals to the critical load. See paragraph 3.2.5 for wiring and termination requirements. 12. Proceed to paragraph 4.8.3. ® ® 4-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 85: Figure 4-13. Distributed Bypass Wire Length

    1A = 2A = 3A = 4A 1B = 2B = 3B = 4B Figure 4-13. Distributed Bypass Wire Length ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-17...
  • Page 86: Figure 4-14. Isbm Section Power Terminal Locations (380V, 400V, 415V, And 480V Models)

    UPS Input UPS Output Battery (+) Battery (-) Bypass Input Figure 4-14. ISBM Section Power Terminal Locations (380V, 400V, 415V, and 480V Models) ® ® 4-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 87: Figure 4-15. Isbm Section Power Terminal Locations (600V Models)

    Installation UPS Input UPS Output Battery (+) Battery (-) Bypass Input Figure 4-15. ISBM Section Power Terminal Locations (600V Models) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-19...
  • Page 88: Figure 4-16. Isbm Section Power Terminal Detail - Section Aa (380V, 400V, 415V, And 480V Models)

    Phase B (E7) UPS Bypass Phase C (E8) Figure 4-16. ISBM Section Power Terminal Detail – Section AA (380V, 400V, 415V, and 480V Models) ® ® 4-20 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 89: Battery Power Wiring

    Se reporter au chapitre 10 sur les notices techniques pour connaître les tensions maximales du chargeur de batteries.Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et communiquer avec un représentant du service Eaton immédiatement. To install wiring to connections:...
  • Page 90: Installing Interface Connections

    Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. AVERTISSEMENT! Des tensions dangereuses sont présentes près de l’enceinte du terminal de l’interface utilisateur si l’onduleur n’est pas totalement débranché. ® ® 4-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 91: Tb1, Tb2, And Tb3 Connections (Other Than Tb1 Battery Interface Connections)

    11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-23...
  • Page 92: Figure 4-18. Isbm Section Interface Terminal Locations

    X-Slot Communication Bays (See Figure 4‐16 for detail.) TB1, TB2, and TB3 (See Figure 4‐11 for detail.) Figure 4-18. ISBM Section Interface Terminal Locations. ® ® 4-24 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 93 Building Alarm 5 Return NOTE “Return“ indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-25...
  • Page 94: Figure 4-19. Interface Terminal Detail

    NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG. Figure 4-20. Typical Alarm Relay Connection ® ® 4-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 95: Figure 4-21. Terminal Blocks Tb1, Tb2, And Tb3 Connector Assignments

    NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Figure 4-21. Terminal Blocks TB1, TB2, and TB3 Connector Assignments ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-27...
  • Page 96: Tb1 Battery Interface Connections

    11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. If wiring X-Slot connections, proceed to paragraph 4.9.3; otherwise, proceed to Step 13. 13. Close the door and secure the latch. ® ® 4-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 97: Figure 4-22. Typical Battery Interface Connection - Common Battery System

    NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. Figure 4-23. Typical Battery Interface Connection – Separate Battery System ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-29...
  • Page 98: X-Slot Connections

    When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). To install wiring to connections: If not already installed, install the LAN drops.
  • Page 99: Installing A Repo Switch

    The REPO switch must be a normally-open or normally-closed latching-type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide.
  • Page 100: Figure 4-26. Repo Switch

    Tightening Torque (Either Block) UPS Cabinet 3 NO TB1-3 Twisted Wires (2) 14–22 AWG 7 lb in (0.75–4.0 mm2) (0.8 Nm) 4 NO TB1-4 ® ® 4-32 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 101: Figure 4-27. Normally-Open Repo Switch Wiring

    Figure 4-28 shows the wiring connections if the normally-closed REPO contacts are used and Figure 4-29 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 4-33...
  • Page 102: Figure 4-28. Normally-Closed Repo Switch Wiring

    NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Figure 4-29. Normally-Closed and Normally-Open REPO Switch Wiring ® ® 4-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 103: Installing Options, Accessories, And Distributed Bypass Control Wiring

    W-1 become void. This service is offered as part of the sales contract for the UPS. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 104: Installation Checklist

    Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) The debris shields covering the UPS cabinet ventilation grills are removed. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. ®...
  • Page 105: Distributed Bypass Installation Checklist

    Controller Area Network (CAN) wiring between the UPS cabinets is properly installed. Pull-chain wiring between the UPS cabinets is properly installed. Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. ® ®...
  • Page 106 Distributed Bypass Installation Checklist This page intentionally left blank. ® ® 4-38 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 107: Installing Options And Accessories

    Hot Sync CAN Bridge card (see paragraph 5.1) Parallel system wiring (see paragraph 5.2) RMP II (see paragraph 5.3) RIM II (see paragraph 5.4) SCM II (see paragraph 5.5) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 108: Installing An Optional Hot Sync Can Bridge Card

    Figure 4-18 and Figure 4-24 for X-Slot communication bay locations. To locate the appropriate terminals on the Hot Sync CAN Bridge Card, see Figure 5-2 and Table 5-1. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 109: Figure 5-2. Hot Sync Can Bridge Card Connections

    Normally-open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L Can H CAN input for parallel operation. Shield ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 110: Installing Distributed Bypass Control Wiring

    NOTE Setup of the Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the top internal safety shield panel and secure with the retained hardware.
  • Page 111: Figure 5-3. Distributed Bypass System Can And Pull-Chain Simplified Interface Wiring

    J3–8 (L) J3–8 (L) J3–8 (L) J3–8 (L) J3–9 (H) J3–9 (H) J3–9 (H) J3–9 (H) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) J3–10 (Shield) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 112: Figure 5-5. Distributed Bypass Pull-Chain Wiring Without Mobs

    (Pull Chain) (Pull Chain) (Pull Chain) (Pull Chain) TB2–2 TB2–2 TB2–2 TB2–2 (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 113: Figure 5-6. Distributed Bypass Pull-Chain Wiring With Mobs

    NOTE Use twisted pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Figure 5-6. Distributed Bypass Pull-Chain Wiring with MOBs ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 114: Installing An Optional Remote Monitor Panel

    Remove the ISBM cabinet top right interface conduit landing plate to drill or punch conduit holes (see Figure 4-12). Reinstall the conduit landing plate. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 115: Figure 5-7. Remote Monitor Panel Ii And Relay Interface Module Ii Terminal Locations

    Terminal TB1 Signal Connections from the UPS Terminal TB3 120 Vac Power Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 116: Figure 5-8. Remote Monitor Panel Ii, Relay Interface Module Ii, Or Supervisory Contact Module Ii Wiring

    If all connections are secure but the RMP II continues to self-test, replace the fuse with the spare included in the hardware kit. If a fuse replacement does not correct the problem, contact an Eaton service representative for verification that the RMP II is working correctly.
  • Page 117: Installing An Optional Relay Interface Module

    Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior to making connections with J1 through J4 (see Table 5-6 and Figure 5-9).
  • Page 118: Installing An Optional Supervisory Contact Module Ii

    Install 120 Vac power wiring from the critical bus to the SCM II. See Figure 5-10, Figure 5-8, and Table 5-5 for the terminal location and wiring information. ® ® 5-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 119: Figure 5-10. Supervisory Contact Module Ii Terminal Location

    Connections from the UPS Figure 5-10. Supervisory Contact Module II Terminal Location NOTE Setup of the Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date.
  • Page 120: Accessory Mounting Dimensions

    Accessory Mounting Dimensions Figure 5-12 through Figure 5-14 show the dimensions of the RMP II, the RIM II, and the SCM II. ® ® 5-14 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 121: Figure 5-12. Remote Monitor Panel Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-12. Remote Monitor Panel II Dimensions ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 5-15...
  • Page 122: Figure 5-13. Relay Interface Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-13. Relay Interface Module II Dimensions ® ® 5-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 123: Figure 5-14. Supervisory Contact Module Ii Dimensions

    Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Figure 5-14. Supervisory Contact Module II Dimensions ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 5-17...
  • Page 124 Installing Options and Accessories This page intentionally left blank. ® ® 5-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 125 Section II Operation...
  • Page 127: Understanding Ups Operation

    Chapter 6 Understanding UPS Operation UPS System Overview The Eaton Power Xpert 9395P-300 UPS is a continuous-duty, solid-state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 128: Single Ups

    DC voltage charge current to the battery. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 129: Figure 6-2. Path Of Current Through The Ups In Online Mode

    If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 130: Energy Saver System (Ess) Mode

    (customer configurable). At the completion of the hour, the UPS defaults back to VMMS mode. If the High Alert command is received during the one hour, the one hour timer will be restarted. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 131: Bypass Mode

    K3 opens to isolate the inverter. The backfeed protection contactor is normally closed, ready to support the static switch unless the bypass input source becomes unavailable ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 132: Battery Mode

    DC voltage level is reached where the inverter output can no longer support the shared loads. If the bypass source is available, the UPS transfers to bypass instead of shutting down. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 133: Figure 6-4. Path Of Current Through The Ups In Battery Mode

    NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Figure 6-4. Path of Current Through the UPS in Battery Mode ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 134: Single Ups Unit System Oneline Configurations

    Single Reverse Transfer UPS – One UPM, Common Rectifier Feed, Battery System, IOM page 15 Eaton 9395P-300/275 Configuration Eaton 9395P-300/250 Eaton 9395P-300/225 Eaton 9395P-300/200 ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 135 Single Reverse Transfer UPS – Two UPM, Common Rectifier Feed, Common Battery, IOM Configuration page 18 Eaton 9395P-300/275 Eaton 9395P-300/250 Eaton 9395P-300/225 Eaton 9395P-300/200 ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 136: Figure 6-5. One Upm, Rectifier Feed, Battery System, Dual-Feed Configuration, Continuous Static Switch

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. Figure 6-5. One UPM, Rectifier Feed, Battery System, Dual-Feed Configuration, Continuous Static Switch ® ® 6-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 137: Figure 6-6. One Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch, Fi-Upm

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. Figure 6-6. One UPM, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch, FI-UPM ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-11...
  • Page 138: Figure 6-7. One Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static Switch, Fi-Upm

    Tables 3-7, 3-9, 3-11, 3-13, 3-15 or 3-17. , and Figure 6-7. One UPM, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static Switch, FI-UPM ® ® 6-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 139: Figure 6-8. Two Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. Figure 6-8. Two UPM, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-13...
  • Page 140: Figure 6-9. Two Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static Switch

    Tables 3-7, 3-9, 3-11, 3-13, 3-15 or 3-17. Figure 6-9. Two UPM, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration, Continuous Static Switch ® ® 6-14 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 141: Figure 6-10. One Upm, Rectifier Feed, Battery System, Iom Configuration

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. Figure 6-10. One UPM, Rectifier Feed, Battery System, IOM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-15...
  • Page 142: Figure 6-11. One Upm, Common Rectifier Feed, Common Battery, Iom Configuration, Fi-Upm

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. Figure 6-11. One UPM, Common Rectifier Feed, Common Battery, IOM Configuration, FI-UPM ® ® 6-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 143: Figure 6-12. One Upm, Common Rectifier Feed, Separate Battery, Iom Configuration, Fi-Upm

    Tables 3-7, 3-9, 3-11, 3-13, 3-15 or 3-17. Figure 6-12. One UPM, Common Rectifier Feed, Separate Battery, IOM Configuration, FI-UPM ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-17...
  • Page 144: Figure 6-13. Two Upm, Common Rectifier Feed, Common Battery, Iom Configuration

    Tables 3-6, 3-8, 3-10, 3-12, 3-14 or 3-16. , and Figure 6-13. Two UPM, Common Rectifier Feed, Common Battery, IOM Configuration ® ® 6-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 145: Figure 6-14. Two Upm, Common Rectifier Feed, Separate Battery, Iom Configuration

    Tables 3-7, 3-9, 3-11, 3-13, 3-15 or 3-17. , and Figure 6-14. Two UPM, Common Rectifier Feed, Separate Battery, IOM Configuration ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-19...
  • Page 146: Figure 6-15. Simplified Dual-Feed Ups With Maintenance Bypass Panel

    (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Figure 6-15. Simplified Dual-Feed UPS with Maintenance Bypass Panel ® ® 6-20 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 147: Multiple Ups Distributed Bypass System

    The UPSs switch operating modes in response to these system events: ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-21...
  • Page 148: Online Mode - Distributed Bypass

    Closed Output to Main Power Flow Critical Load Open Figure 6-16. Path of Current through the UPSs in Online Mode - Distributed Bypass ® ® 6-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 149: Bypass Mode - Distributed Bypass

    Closed Output to Main Power Flow Critical Load Open Figure 6-17. Path of Current through the UPSs in Bypass Mode - Distributed Bypass ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-23...
  • Page 150: Battery Mode - Distributed Bypass

    When this event occurs, the system shuts down. If the bypass source is available, the system transfers to bypass instead of shutting down. ® ® 6-24 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 151: Figure 6-18. Path Of Current Through The Upss In Battery Mode - Distributed Bypass

    ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-25...
  • Page 152: Multiple Ups Distributed Bypass System Oneline Configurations

    Eaton 9395P-300/300 Multiple UPS – Distributed Bypass, Continuous Static Switch, 3+1 and 4+0 Configurations page 29 Eaton 9395P-300/275 Eaton 9395P-300/250 Eaton 9395P-300/225 Eaton 9395P-300/200 ® ® 6-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 153: Figure 6-19. Typical Distributed Bypass System - Continuous Static Switch, 1+1 And 2+0 Configurations

    UPS is shown in Figure 6‐5. Figure 6-19. Typical Distributed Bypass System - Continuous Static Switch, 1+1 and 2+0 Configurations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-27...
  • Page 154: Figure 6-20. Typical Distributed Bypass System -Continuous Static Switch, 2+1 And 3+0 Configurations

    Critical Load structure of each UPS is shown in Figure 6‐5. Figure 6-20. Typical Distributed Bypass System -Continuous Static Switch, 2+1 and 3+0 Configurations ® ® 6-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 155: Figure 6-21. Typical Distributed Bypass System -Continuous Static Switch, 3+1 And 4+0 Configurations

    Critical Load structure of each UPS is shown in Figure 6‐5. Figure 6-21. Typical Distributed Bypass System -Continuous Static Switch, 3+1 and 4+0 Configurations ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 6-29...
  • Page 156 Understanding UPS Operation This page intentionally left blank. ® ® 6-30 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 157: Ups Operating Instructions

    The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 7.3. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 158: Figure 7-2. Ups Color Touchscreen Control Panel (Typical)

    A horizontal row of LED indicators (2) Before system power up, the panel displays a system status screen similar to the one shown in Figure 7-2. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 159: Status Indicators

    Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right corner of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password request pop-up (see Figure 7-4). ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 160: Figure 7-3. Parts Of The Touch Screen

    UPS Operating Instructions Figure 7-3. Parts of the Touch Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 161: Figure 7-4. Sign In Or Password Request Screen

    The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
  • Page 162: Figure 7-5. Home Screen

    Yellow lines indicates an out-of-tolerance condition. NOTE Screens shown are representative examples of system operation. The screen data will vary based on system activity at the time of observation. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 163: Figure 7-6. Main Menu And Power Maps Screen (Online Mode)

    Figure 7-6. Main Menu and Power Maps Screen (Online Mode) Touching the LOAD kVA button displays the Output kVA screen shown in Figure 7-7. Figure 7-7. Output kVA Screen from Home Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 164: Figure 7-8. Average Efficiency Screen From Home Screen

    Figure 7-8. Average Efficiency Screen from Home Screen Touching the CONSUMPTION button displays the screen shown in Figure 7-9. Figure 7-9. Consumption Screen from Home Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 165: Figure 7-10. Bypass Screen

    Figure 7-11 is an example of a command request confirmation pop-up screen. This type of pop-up allows the user to confirm that the requested command is valid. Figure 7-11. Typical Command Confirmation Screen (Charger Off) ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 166: Figure 7-12. Meters Summary Screen

    24 hours, 7 days, 30 days, or 1 year. This is true of all the meters screens listed in the top section. Figure 7‐8 Figure 7‐9 Figure 7-12. Meters Summary Screen ® ® 7-10 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 167: Figure 7-13. Input Meters Screen

    Figure 7-13. Input Meters Screen The Bypass Meters Screen shown in Figure 7-14 displays values pertaining to the Bypass conditions. Figure 7-14. Bypass Meters Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-11...
  • Page 168: Figure 7-15. Output Meters Screen

    UPS Operating Instructions The Output Meters Screen shown in Figure 7-15 displays values pertaining to the system output. Figure 7-15. Output Meters Screen ® ® 7-12 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 169: Figure 7-16. Input Meters Detail Screen

    The Select Source screen shown in Figure 7-17allows the operator to choose the individual source for system readings. Figure 7-17. Select Source Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-13...
  • Page 170: Figure 7-18. Battery Meters Screen

    Figure 7-18 shows the Battery Meters basic screen. Figure 7-19 shows the Battery Log access screen. Figure 7-18. Battery Meters Screen Figure 7-19. Battery Log Screen ® ® 7-14 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 171: Figure 7-20. Battery Log Detail

    Figure 7-20 shows the Battery Log Detail screen. Figure 7-21 shows the Battery Log Summary screen. Figure 7-20. Battery Log Detail Figure 7-21. Battery Log Summary Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-15...
  • Page 172: Figure 7-22. System Events Screen

    This message is also written to the Active Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands. ® ® 7-16 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 173: Figure 7-23. User Log Screen

    Selecting an event opens the Event Detail screen shown in Figure 7-24. This screen details the specifics of the event for the user to see. Figure 7-24. User Log Detail Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-17...
  • Page 174: Figure 7-25. System Status Screen

    Figure 7-26 shows the Module Controls screen. This screen allows control of the individual modules within the system. It also gives their values and status. Figure 7-26. Module Controls Screen ® ® 7-18 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 175: Figure 7-27. Module Control Detail Screen

    The Metering Method screen allows the operator to select line-to-line or line-to-neutral monitoring values. See Figure 7-28 or Figure 7-29. Figure 7-28. Online Mode Metering Method Option Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-19...
  • Page 176: Figure 7-29. Bypass Mode Metering Method Option Screen

    Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Figure 7-30. Settings Screen ® ® 7-20 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 177: Figure 7-31. Configuration Options Screen

    The various Energy Advantage Architecture operations are described in the UPS Installation and Operation manual for your system. Figure 7-32. Energy Advantage Architecture (EAA) Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-21...
  • Page 178: Figure 7-33. Disable Ess Screen

    Figure 7-34. High Alert Timer Screen This screen shown in Figure 7-34 asks the operator if they want to start the High Alert mode timer. ® ® 7-22 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 179: Figure 7-35. Statistics Basic Screen

    The screen shown in Figure 7-35 allows the operator to query the system for various operational statistics such as shown in Figure 7-36. Figure 7-35. Statistics Basic Screen Figure 7-36. Statistics Data Detail Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-23...
  • Page 180: Figure 7-37. Ess Comparison Screen

    7.3.19 UPS Module Map Screen The screen shown Figure 7-38 allows the operator to control the individual UPMs. Figure 7-38. UPS Module Map Screen ® ® 7-24 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 181: Figure 7-39. System Overview Screen

    UPS Operating Instructions 7.3.20 System Overview Screen The screen shown Figure 7-39 displays values for all UPS and UPM parameters. Figure 7-39. System Overview Screen ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-25...
  • Page 182: Ups Operation Using The Color Touchscreen Control Panel

    UPS control panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Online mode. ® ® 7-26 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 183: Using The Remote Emergency Power-Off Switch

    à l’étape suivante. N’utiliser cette fonction que pour mettre la charge critique hors tension. NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 184: Figure 7-40. Repo Operation

    L ’intérieur de l’armoire de l’onduleur est alimenté jusqu’à ce que le disjoncteur du circuit d’alimentation en amont soit activé. Activated Deactivated Pushbutton locked into place Unlock pushbutton to release Figure 7-40. REPO Operation ® ® 7-28 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 185: Multiple Ups Distributed Bypass Operation

    The UPM status indicates ONLINE, CHARGING on the MIMIC Screen. 17 . To activate, enable, or disable any of the UPS operational modes, follow the online screen prompts. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-29...
  • Page 186: Starting The Distributed Bypass System In Bypass Mode

    Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, the UPS status should indicate SHUTDOWN and the UPM status should indicate OFFLINE. ® ® 7-30 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 187: Single Upm Shutdown

    Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the UPM command. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-31...
  • Page 188: Single Ups Shutdown Using Load Off

    The input, output, battery, and bypass backfeed contactors open, and the power module is turned off on the UPS being shut down. Logic power remains on. ® ® 7-32 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 189: Single Ups Shutdown Using Upm Shutdown

    UPMs are shut down. 12. Perform the LOAD OFF procedure in paragraph 7.5.11 or paragraph 7.5.12 on the UPS being shut down. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-33...
  • Page 190: Single Ups Restart

    13. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is displayed. 14. On the UPS Control Command screen, select GO TO ONLINE. ® ® 7-34 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 191: Ups And Critical Load Shutdown

    On the Charger Control Command screen, select CHARGER ON. Press the SELECT pushbutton on the Charger Command menu bar. To turn off the battery charger: ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-35...
  • Page 192: Using The Ups Load Off Pushbutton

    Restart the UPS after pressing the LOAD OFF pushbutton by following the procedure in paragraph 7.5.1 or 7.5.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. ® ® 7-36 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 193: Using The Ups Load Off Command

    Restart the UPS by following the procedure in paragraph 7.5.1 or 7.5.2. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 7-37...
  • Page 194: Using The Remote Emergency Power-Off Switch

    NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 195: Figure 8-1. Optional X-Slot Cards

    LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to the manual supplied with the X-Slot card for user instructions.
  • Page 196: Predictpulse

    Real-time alarm events for all subscribed devices via the PredictPulse mobile app (Apple and Android). You can track all alarms by device. As critical alarms occur, Eaton will acknowledge them so you know when Eaton has diagnosed the alarm (and pending notification of resolution).
  • Page 197: General Purpose Relay Contact

    Management Software for UPS management and monitoring, and Eaton LanSafe software, which allows graceful shutdown of operating systems. Eaton’s Intelligent Power Software gives you all the tools you need to monitor and manage power devices on your network, even in a virtualized environment. This innovative software solution combines the most critical applications in ensuring system uptime and data integrity: not only power monitoring and management, but also graceful shutdown during an extended power outage.
  • Page 198: Remote Monitor Panel Ii

    The RMP II can be flush-mounted or surface-mounted on a desktop, or secured to a wall. Figure 8-2 shows an RMP II. Figure 8-2. Remote Monitor Panel II ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 199 The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This indicator is accompanied by a horn. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 200: Relay Interface Module

    BATTERY WEAK Pins 5 and 14 critical load is lost. UTILITY FAILURE Pins 6 and 15 Contacts are closed when Utility Failure is detected. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 201: Supervisory Contact Module Ii

    BYPASS NOT AVAILABLE TB2-10 through TB2-12 ON BATTERY TB2-13 through TB2-15 UPS ALARM TB2-16 through TB2-18 ON BYPASS TB2-19 through TB2-21 SHUTDOWN IMMINENT TB2-22 through TB2-24 ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 202 Communication This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 203: Ups Maintenance

    THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative.
  • Page 204: Performing Preventive Maintenance

    Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See Figure 9-1 and Figure 9-2 for filter locations, and Table 9-1 for filter sizes. Contact an Eaton service representative for replacement filters. To remove and replace the filters: Table 9-1.
  • Page 205: Figure 9-1. Isbm And Upm Section Air Filter Locations - Continuous Static Switch

    If the UPS configuration included an FI-UPM model, check the FI-UPM air filter (located behind the front panel) and wash or replace as necessary. See Figure 9-2 for the filter location. The FI-UPM filter size is 20” X 44” X 0.25” . Contact an Eaton service representative for a replacement filter. To remove the filter: ®...
  • Page 206: Figure 9-2. Fi-Upm Air Filter Location

    UPS Maintenance ® Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton ® Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)). Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
  • Page 207: Periodic Maintenance

    9.2.4 ANNUAL Maintenance Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings. 9.2.5 BATTERY Maintenance Contact an Eaton service representative for battery maintenance.
  • Page 208: Installing Batteries

    Ne pas éliminer les déchets d’équipements électriques et électroniques (DEEE) aux ordures. Pour connaître la méthode d’élimination appropriée, communiquer avec le centre régional de récupération/réutilisation ou d’élimination des déchets dangereux. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 209: Maintenance Training

    UPS Maintenance Maintenance Training A basic training course, available from Eaton, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Eaton Help Desk (see page 1-10).
  • Page 210 UPS Maintenance This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 211: Product Specifications

    The UPS is housed in one or two free-standing cabinets with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various output power ratings. Power Models Rating Frequency Eaton 9395P-300/300 (one or two UPM) 300 kVA, 50/60 Hz 300 kW Eaton 9395P-300/275 (one or two UPM) 275 kVA,...
  • Page 212: 10.2.2 Ups Output

    .7 Hz per second maximum Load Compatibility 0.9 pF Leading 0.7 pF Lagging Overload Capability 110% for 10 minutes 125% for 120 seconds 150% for 15 seconds ® ® 10-2 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 213: 10.2.3 Ups Environmental

    Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without Immunity damage and with no disturbance or adverse effect to the critical load. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality 10-3...
  • Page 214 Product Specifications This page intentionally left blank. ® ® 10-4 Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...
  • Page 215: Warranty

    Eaton-built battery cabinets, (individually and collectively, the “Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted Item is defective and the defect is within the terms of this Warranty, Eaton's sole obligation will be to repair or replace such defective item (including by providing service, parts and labor, as applicable), at the option of Eaton.
  • Page 216 Warranty This page intentionally left blank. ® ® Eaton Power Xpert 9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality...