Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes.
Do not tilt the cabinets more than ±10° during installation.
Remove the conduit landing plates to add conduit landing holes as required. Plate material is 16 gauge
steel (1.5 mm/0.06" thick).
If perforated floor tiles are required for ventilation, place them in front of the UPS.
4 4 . . 2 2
U U n n l l o o a a d d i i n n g g t t h h e e U U P P S S C C a a b b i i n n e e t t f f r r o o m m t t h h e e P P a a l l l l e e t t
The ISBM and UPM sections are bolted to separate wooden pallets supported by wood skids. To remove the
pallets:
The UPS sections are heavy (see
cabinets may tip and cause serious injury.
Do not tilt cabinets more than 10° from vertical.
Lift the cabinets only with a forklift or damage may occur.
To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the
cabinet:
Lift and move the UPM section using only the front or rear forklift slots.
Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots. DO NOT
angle fork tips upward.
Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.
Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are kept
in a horizontal position with no upward angling.
DO NOT use the forklift slots on the end of the cabinet to move the cabinet.
End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.
If these instructions are not followed, damage to the wiring channel and wiring will occur.
Table
NOTE
For the following steps, verify that the forklift or pallet jack is rated to handle the weight
of the cabinet (see
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
2). If unpacking and unloading instructions are not closely followed, the
Table
2) for cabinet weight).