Eaton Power Xpert 9395 Installation And Operation Manual page 164

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Table 32. Typical System Status Messages
UPS
UPS
Bypass
Maintenance Bypass
Charger
UPM (during startup)
UPM 1
UPM 4 (if FI-UPM is installed)
Table 33. Command Menu Operation
Function
Sub-function
UPS Control
Commands
Go to Online
Enable (Disable) Energy Saver
Enable (Disable) Var Module Management
Start High Alert
Go to Bypass
Load Off
Bypass
Commands
Go to Bypass
Go to Online
Enable (Disable) Energy Saver
Message
Shutdown; Bypass; Online; Online with ESS; Online +VMMS; High Alert
Off; On; Available
Off; On
Charger Off; Charging
DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting; Inverter
Syncing; Ready; Online
Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online, Charger Off; Online,
Charging
Operation
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command or proceed to further
command screens.
Starts the UPS in Online mode or transfers the UPS to Online
mode from Bypass mode.
Enables or disables Energy Saver System mode. Enable
changes to Disable when the Energy Saver System mode is
enabled.
Enables or disables the Variable Module Management
System mode. Enable changes to Disable when the Variable
Module Management System mode is enabled.
Starts High Alert mode.
Starts the UPS in Bypass mode or transfers the UPS to
Bypass mode from Online mode.
Displays the Load Off screen (see paragraph
7.2.7 Load Off
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command or proceed to further
command screens.
Starts the UPS in Bypass mode or transfers the UPS to
Bypass mode from Online mode.
Starts the UPS in Online mode or transfers the UPS to Online
mode from Bypass mode.
Enables or disables Energy Saver System mode. Enable
changes to Disable when the Energy Saver System mode is
enabled.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Operating Instructions
Screen).
143

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395p

Table of Contents