UPS Operating Instructions
14. Press the SELECT pushbutton on the UPM 1 Command menu bar. The UPM status indicates SHUTDOWN.
The power module is turned off. Logic power remains on.
15. If UPM 4 (FI-UPM) is installed, repeat Steps 5 through 14 selecting UPM 4 to shut down UPM 4.
16. Repeat Steps 2 through 15 for each UPS in the distributed bypass system.
Power is present inside the UPS cabinet.
7 7 . . 4 4 . . 2 2 0 0 S S i i n n g g l l e e U U P P M M S S h h u u t t d d o o w w n n
To shut down a single UPM:
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the UPM Command. The UPS Control Command screen is displayed.
4.
On the UPS Control Command screen, select the UPM to shut down.
5.
Press the CONTROLS pushbutton on the UPS Control Command menu bar. The UPM Control Command
screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the UPM command.
8.
Press the CONTROLS pushbutton on the System Status Command menu bar. The UPM Control
Command screen is displayed.
9.
On the UPM Control Command screen, select UPM OFF.
10. Press the SELECT pushbutton on the UPM Command menu bar. The UPM status indicates READY. The
input, output, and battery contactors open, and the power module remains on. The remaining UPMs
supply the critical load.
11. To turn off the power module, press the CONTROLS pushbutton on the UPS Control Command menu bar.
The UPM Control Command screen is displayed.
12. On the UPM Control Command screen, select UPM OFF.
13. Press the SELECT pushbutton on the UPM Command menu bar.
The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to
supply the critical load.
Logic power remains on.
7 7 . . 4 4 . . 2 2 1 1 S S i i n n g g l l e e U U P P M M R R e e s s t t a a r r t t
To restart a single UPM from a shutdown state:
1.
Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the UPM command. The UPS Control Command screen is displayed.
4.
On the UPS Control Command screen, select the UPM to restart.
5.
Press the CONTROLS pushbutton on the UPS Control Command menu bar. The UPM Control Command
screen is displayed.
170
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14