Eaton Power Xpert 9395 Installation And Operation Manual page 84

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Figure 29. J39 Location on Pl1 Interface Board
4 4 . . 5 5
F F i i e e l l d d I I n n s s t t a a l l l l e e d d U U P P M M I I n n s s t t a a l l l l a a t t i i o o n n
NOTE
If installing a four UPM model, install the FI-UPM using the instructions in the Power Xpert 9395 Field Installed
UPM Mechanical Installation Manual, listed in paragraph
installed, proceed to paragraph
to paragraph
4 4 . . 6 6
B B a a t t t t e e r r y y S S y y s s t t e e m m I I n n s s t t a a l l l l a a t t i i o o n n
If installing a battery system, install the customer-supplied battery system according to the battery and battery
system manufacturer's instructions and all applicable codes and regulations, including the NEC, Article 480.
After the battery system is installed, proceed to paragraph
installing a distributed bypass tie cabinet; otherwise, proceed to paragraph
4.8 Installing UPS External and Battery Power Wiring
4 4 . . 7 7
D D i i s s t t r r i i b b u u t t e e d d B B y y p p a a s s s s T T i i e e C C a a b b i i n n e e t t I I n n s s t t a a l l l l a a t t i i o o n n
NOTE
If installing a distributed bypass system, install the customer-supplied tie cabinet or distribution panel according
to the tie cabinet or distribution panel manufacturer's instructions and all applicable codes and regulations,
including the NEC, Article 480. After the tie cabinet is installed, proceed to paragraph
4.8 Installing UPS External and Battery Power Wiring
In the case of parallel Distributed Bypass configurations, wiring for the common system neutral reference will
also be connected to E12 of each module and this common system neutral reference wiring will be routed to
the output switchgear cabinet and connected to an isolated / ungrounded bus which is common with the wiring
from the E12 terminal of all other paralleled modules of the Distributed Bypass system.
FI-UPM installation is not applicable to a three UPM model.
4.6 Battery System Installation
4.7 Distributed Bypass Tie Cabinet Installation
The tie cabinet must contain Module Output Breakers (MOBs) with dual auxiliary
contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed
to go to bypass individually during servicing. All UPMs will go to bypass instead of the
just the UPM needing service, decreasing critical load protection. With dual auxiliary
MOBs, one UPM can be bypassed while the remaining UPMs support the load as long
as the remaining UPMs have the capacity to do so.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
1.7 For More
Information. After the FI-UPM is
if installing a battery system; otherwise, proceed
to complete the wiring of the UPS.
4.7 Distributed Bypass Tie Cabinet Installation
to complete the wiring of the UPS.
to complete the wiring of the UPS.
UPS System Installation
Pl1 Interface Board
J39 Inverter CAN Connector
if
63