UPS Installation Plan and Unpacking
Do not tilt the UPS cabinet more than 10º from vertical or the cabinet may tip over.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
NOTE
4.
Remove the protective covering from the cabinet.
5.
Remove the packing material, and discard or recycle in a responsible manner.
6.
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.
NOTE
44
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
The ISBM and UPM sections are shipped with debris shields covering the ventilation
grills on top of the sections (see
installation is complete.
While waiting for installation, protect the unpacked cabinet from moisture, dust, and
other harmful contaminants. Failure to store and protect the UPS properly may void your
warranty.
Figure
30). Do not remove the debris shields until