Eaton Power Xpert 9395 Installation And Operation Manual page 48

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Table 5. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000 and 9395-
1100/1100 – Common Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Each Battery Disconnect to Each UPS
UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Pole
A
AWG or kcmil
B
AWG or kcmil
B
AWG or kcmil
Total Amps
C
AWG or kcmil
D
AWG or kcmil
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Installation Plan and Unpacking
Rating 50/60 Hz
Units
kVA
1000
1000
kW
910
910
Volts
400/400
480/480
Amps
1646
1372
500
500
(6)
(5)
(each)
Amps
1443
1203
500
350
(each)
(5)
(4)
Amps
1443
1203
500
500
(each)
(6)
(5)
2000
2000
500
500
(each)
(8)
(8)
Amps
1203
1443
500
350
(each)
(5)
(4)
1000
1000
1001
1001
400/400
480/480
1810
1509
500
500
(6)
(5)
1588
1323
500
500
(5)
(5)
1588
1323
500
500
(6)
(6)
2205
2205
500
500
(9)
(9)
1588
1323
500
500
(5)
(5)
27