Table 34. Status Indicators
Indicator
Green
Yellow
Yellow
Red
7 7 . . 6 6 . . 2 2 U U s s i i n n g g t t h h e e T T o o u u c c h h S S c c r r e e e e n n
The touch screen control panel provides an operator interface with the UPS system.
display areas discussed in the following sections.
Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right corner
of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password request pop-up
(see
Figure
89).
Description
Status
Lit Steady
The UPS is in Online mode, operating normally. The power module is
supplying power to the critical load.
Lit Steady
The UPS is in Battery mode. Because Battery mode is a normal condition of
the UPS, the Online indicator also remains illuminated.
Lit Steady
The UPS is in Bypass mode. The critical load is supported by the bypass
source. The Online indicator is not illuminated when the system is in Bypass
mode.
Lit Steady
The UPS has an active alarm and requires immediate attention. The screen
shows the highest priority active alarms. All alarms are accompanied by an
audible horn. To silence the horn, press any control panel pushbutton once.
The Alarm indicator may be illuminated along with other indicators.
Lit Flashing
There is a new UPS alarm condition. The indicator flashes until
acknowledged by pressing any control panel pushbutton once.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Operating Instructions
Figure 88
identifies the
179