Installation
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.

Figure 4-28. Normally-Closed REPO Switch Wiring

NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.

Figure 4-29. Normally-Closed and Normally-Open REPO Switch Wiring

®
4-34
Eaton
Power Xpert
1
REPO
Switch
(NC)
2
T
he REPO switch must be a latching-type switch not tied to any other circuits.
REPO
Switch
(NC)
REPO
Switch
(NO)
T
he REPO switch must be a latching-type switch not tied to any other circuits.
®
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality
1 (NC)
Twisted
Wires
2 (Return)
UPS TB1
3 (NO)
4 (Return)
1 (NC)
2 (Return)
UPS TB1
3 (NO)
Twisted
Wires
4 (Return)