Eaton Power Xpert 9395 Installation And Operation Manual page 165

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

UPS Operating Instructions
Table 33. Command Menu Operation (Continued)
Function
Charger Control
Commands
UPM Control
Commands
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.
7 7 . . 3 3
S S i i n n g g l l e e U U P P S S O O p p e e r r a a t t i i o o n n
The paragraphs in this section provide operating instructions for a UPS system containing only one UPS.
NOTE
7 7 . . 3 3 . . 1 1 S S t t a a r r t t i i n n g g t t h h e e U U P P S S i i n n O O n n l l i i n n e e M M o o d d e e
To start the UPS system:
1.
Unfasten the front door latch and swing the door open (see
NOTE
2.
*Verify that input breaker CB1 is open.
3.
Close the UPS input feeder circuit breaker.
4.
Close the UPS Bypass input feeder circuit breaker.
5.
*Close input breaker CB1.
144
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Sub-function
Enable (Disable) Var Module Management
Start High Alert
Load Off
Charger On
Charger Off
UPM On
UPM Off
UPM Go to Online
Charger On
Charger Off
A Field Installed UPM (FI-UPM) is always designated as UPM 4.
*Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see
Operation
Enables or disables the Variable Module Management
System mode. Enable changes to Disable when the Variable
Module Management System mode is enabled.
Starts High Alert mode.
Displays the Load Off screen (see paragraph
7.2.7 Load Off
Screen).
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command.
Turns the battery charger on.
Turns the battery charger off.
Use the up or down arrow pushbutton to highlight the
command function desired, then press the SELECT
pushbutton to execute the command.
Turns the UPM on without transferring the load to Online
mode. The Load is on bypass.
Transfers the load to bypass and turns the UPM off.
Turns the UPM on and transfers the load to Online mode.
Turns the battery charger on.
Turns the battery charger off.
Figure
17).
Figure
79).

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power xpert 9395p

Table of Contents