UPS Operating Instructions
Table 31. Display Menu Operation
Function
Events
User History
Service History
Meters UPS
Meters UPM
138
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Sub-function
Operation
Press the EVENTS pushbutton on the main menu bar or History menu bar to display a
listing of all system events that are currently active. The most recent event is listed first.
As events clear, they are removed from the Active System Events listing. To scroll through
the events, press the up or down arrow pushbutton on the menu bar.
Press the HISTORY pushbutton on the Active Events menu bar to display the User History
Log. The User History Log lists up to 2048 events in chronological order, with the most
recent event listed last (once 2048 is reached, the earliest event is overwritten). The end
of the log (the most recent events) is displayed first; scroll upward to view older event
listings. To scroll through the events, press the up or down arrow pushbutton on the menu
bar. To return to the Active Events screen, press the EVENTS pushbutton on the menu
bar.
The Service History Log is for service personnel and is password protected. If the customer
needs access to the log, contact an Eaton service representative.
Press the
SERVICE pushbutton on the User History menu bar to display the Service History Log. The
Service History Log lists up to 2048 events in chronological order, with the most recent
event listed last (once 2048 is reached, the earliest event is overwritten). The end of the
log (the most recent events) is displayed first; scroll upward to view older event listings.
To scroll through the events, press the up or down arrow pushbutton on the menu bar. To
return to the User History screen, press the USER pushbutton on the menu bar. To return
to the Active Events screen, press the EVENTS pushbutton on the menu bar.
The Meter screens show the UPS meter readings for the unit. The default voltage
displayed on these screens is phase-to-neutral. However, an authorized Eaton Customer
Service Engineer can change the screens to display the voltage phase-to-phase (A-B, B-C,
C-A). Press the METERS pushbutton on the main menu bar to display the Meter screens.
To scroll through the meter screens, press the up or down arrow pushbutton on the menu
bar. The current UPS readings are displayed in the information area of the screen.
Output UPS Output
The Output screen shows output voltage (phase to neutral), output current (each phase),
UPM
and frequency being supplied by the UPS, as well as the kVA, kW, and power factor
measurements.
Input UPS
The Input screen shows input voltage (phase to neutral), input current (each phase), and
Input UPM
frequency of the incoming utility source, as well as the kVA, kW, and power factor
measurements.
Bypass
The Bypass screen shows the bypass input voltage (phase to neutral), input current (each
phase), and frequency of the incoming utility source, as well as the kVA, kW, and power
factor measurements.
Battery UPS Battery
The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes
UPM
of battery time remaining, and battery temperature. Battery temperature must be set up by
an authorized Eaton Customer Service Engineer. When battery life decreases to less than
20%, Check Battery is displayed.
Statistics
The Statistics screen displays the hours on line and the total kW hours used.
Output Current UPS
The Output Current screen displays a real time bar graph of the output current of the UPS.
Output Current UPM
The graph shows the current for each phase.
Output Power UPM
The Output Power screen displays the power in kW and kVA for each UPM.