C C h h a a p p t t e e r r 1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s
1 1 0 0 . . 1 1 M M o o d d e e l l N N u u m m b b e e r r s s
The UPS is housed in a free–standing cabinet with safety shields behind the door and front panels. The UPS is
available in 50 or 60 Hz with various output power ratings.
Models
Power Xpert 9395-1100/1000 (four UPM)
Power Xpert 9395-1100/1100 (four UPM)
Power Xpert 9395-1100/650 (four UPM)
Power Xpert 9395-1100/750 (four UPM)
Power Xpert 9395-1100/825 (four UPM)
1 1 0 0 . . 2 2 S S p p e e c c i i f f i i c c a a t t i i o o n n s s
The following sections detail the input, output, battery, and environmental specifications for the UPS.
1 1 0 0 . . 2 2 . . 1 1 U U P P S S I I n n p p u u t t
Operating Input Voltage
Operating Input Frequency Range
Operating Input Current
Input Current Harmonic Content
Power Factor
Line Surges
Battery Voltage
Battery Charging Capacity
Battery Shunt Trip
Power Rating
1000 kVA
1100 kVA
650 kVA
750 kVA
825 kVA
400 Vac
480 Vac
50/60 Hz
See
Table 5
See
Table 7
Reduced for Generator
Adjustable
5% THD at full load
Minimum 0.99
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
480 Vdc
Configurable per UPM at nominal line voltage:
Up to 120A
48 Vdc
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
or
Table 6
for four UPM models.
or
Table 8
for three UPM models.
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz