Eaton Power Xpert 9395 Installation And Operation Manual page 79

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

UPS System Installation
Figure 24. ISBM Section Input Power Terminal Detail
UPM 1 Cable 1G1 & 1G2 Brown
Phase B (E2A)
UPM 4 (FI-UPM) Four UPM Model
UPM 4 (FI-UPM) Four UPM Model
UPM 1 Cable 1G1 & 1G2 Yellow
Phase C (E3A)
UPM 2 Cable 2G1 & 2G2 Yellow
UPM 3 Cable 3G1 & 3G2 Yellow
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised
barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet.
NOTE On a UPS without CB1, UPM input wiring terminations are in the same positions on the bus bars installed in the place of CB1.
NOTE On a UPS configured as an IOM, UPM input wiring terminations are the same as an ISBM configuration.
58
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPM 4 (FI-UPM) Four UPM Model
UPM 1 Cable 1G1 & 1G2 Orange
Phase A (E1A)
UPM 2 Cable 2G1 & 2G2 Orange
UPM 3 Cable 3G1 & 3G2 Orange
UPM 2 Cable 2G1 & 2G2 Brown
Phase B (E2A)
UPM 3 Cable 3G1 & 3G2 Brown
AC Input to UPMs