UPS Installation Plan and Unpacking
•
Select overcurrent protection input, battery, and output breakers according to the UPS nameplate rated for
either 80% or 100%.
•
Follow all applicable NEC and local codes.
For four UPM external wiring requirements, including the minimum AWG size of external wiring, see:
•
Table 5
•
Table 6
Wire sizes listed are for copper wiring only.
For three UPM external wiring requirements, including the minimum AWG size of external wiring, see:
•
Table 7
•
Table 8
Because of the future upgradability to a fully rated 1100 kVA UPS with the adc dition of the FI-UPM, the UPS
wiring is specified for 1100 kVA in
Wire sizes listed are for copper wiring only.
26
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
for common battery system installations
for separate battery system installations
for common battery system installations
for separate battery system installations
Table 7
and
Table
8.