Table 4-5: Normally-Closed REPO Connections and Wire Terminations
From REPO
Station
Switch
Contact
UPS
Block
REPO
(Either Block)
Terminal
1 NC
1
2 NC
2
The REPO switch must be a latching-type switch not tied to any other circuits.
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Name
Description
Input: Normally-closed
dry contact used to
EPO_ A_B
activate UPS
EPO from a remote
switch
GNDISO
Figure 4-19: Normally-Closed REPO Switch Wiring
NOTE
Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
Recommended
Minimum Wire
Size of Wire
Size
Termination
Twisted Pair
#16-#30 AWG
Wires #18 AWG
Tightening
Torque
2 lb in
(0.22-0.25 Nm)
69