Eaton Power Xpert 9395 Installation And Operation Manual

Eaton Power Xpert 9395 Installation And Operation Manual

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Quick Links

Power Xpert
9395 UPS
1000–1100 kVA
Installation and Operation Manual
For use with Three UPM (650–825 kVA) and Four UPM (1000–1100 kVA) UPS Models
p/n: 164201764
Revision 14

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Power Xpert 9395 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton Power Xpert 9395

  • Page 1 Power Xpert ™ 9395 UPS 1000–1100 kVA Installation and Operation Manual For use with Three UPM (650–825 kVA) and Four UPM (1000–1100 kVA) UPS Models p/n: 164201764 Revision 14...
  • Page 2 Association, Inc. All other trademarks are property of their respective companies. All other trademarks are property of their respective companies. ©Copyright 2022 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 Dear Customer, On behalf of everyone at Eaton, we thank you for partnering with us, and trusting us to maintain your business continuity and preventing downtime at your facility. Our suite of backup power, power distribution and power management products are designed to protect you from a host of threats including power outages, surges, lighting strikes, and enable you to monitor and control your power infrastructure.
  • Page 4 Licensee or other subsidiary of Licensee’s parent, to copy, distribute, or otherwise transfer the Firmware without the prior written consent of Eaton. Licensee may transfer the Firmware directly to a third party only in connection with the sale of the Eaton product in which it is installed.
  • Page 5 TO THE EXTENT PERMITTED BY APPLICABLE LAW, THE USE OF THE PRODUCT IS AT LICENSEE’S SOLE RISK. 5.0 GENERAL PROVISIONS 5.1 Update Policy. Eaton may from time to time, but has no obligation to, create Updates of the Firmware or components thereof. 5.2 Limitation on Liability. NOTWITHSTANDING ANY PROVISION OF THIS AGREEMENT TO THE...
  • Page 6 Firmware pursuant to license arrangements between Eaton and such third parties. Third Party Licensor components in the Firmware are not licensed or warranted under the terms of this document, but are instead subject to the Third Party Licensors’...
  • Page 7 Eaton, the disclosure of which would cause substantial harm to Eaton that could not be remedied by the payment of damages alone and such confidential aspects of the Firmware shall not be disclosed to third parties without the prior written consent of Eaton.
  • Page 9 3.2.3 Installation Considerations ........................16 3.2.4 UPS System Power Wiring Preparation ....................24 3.2.5 UPS System Interface Wiring Preparation ....................40 3.2.6 Distributed Bypass Power Wiring Preparation ................... 42 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 10 6.2.6 Bypass Mode........................... 113 6.2.7 Battery Mode........................... 114 6.3 Single UPS System Oneline Configurations ....................116 6.4 Multiple UPS Distributed Bypass System..................... 124 6.4.1 Multiple UPS Parallel System Modes ....................124 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 11 7.3.19 Transfer from Online to Bypass Mode and Shut Down UPMs ..............154 7.3.20 Single UPM Shutdown ........................155 7.3.21 Single UPM Restart ......................... 155 7.3.22 UPS and Critical Load Shutdown ......................156 7.3.23 Charger Control ..........................156 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 12 7.6.4 Power Maps Screen (Online Mode) ...................... 182 7.6.5 Power Maps Screen (Bypass Mode) ..................... 184 7.6.6 Command Confirmation Pop-Up......................185 7.6.7 Meters Summary Screen........................185 7.6.8 Input Meters Screen.......................... 186 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 13 1 1 0 0 P P r r o o d d u u c c t t S S p p e e c c i i f f i i c c a a t t i i o o n n s s ................................................... . 2 2 1 1 5 5 10.1 Model Numbers ........................... 215 10.2 Specifications............................215 10.2.1 UPS Input............................215 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 xiii...
  • Page 14 Table of Contents 10.2.2 UPS Output ........................... 216 10.2.3 UPS Environmental ......................... 216 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 15 ISBM Section Power Terminal Detail BB – Separate Battery ..............73 Figure 37. ISBM Section Interface Terminal Locations..................75 Figure 38. Interface Terminal Detail........................ 77 Figure 39. Typical Alarm Relay Connection....................... 78 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 16: Table Of Contents

    Path of Current through the UPSs in Battery Mode – Distributed Bypass..........128 Figure 76. Typical Distributed Bypass System (1+1 and 2+0 Configurations) ............130 Figure 77. Typical Distributed Bypass System (2+1 and 3+0 Configurations) ............131 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 17 Figure 115. Settings Screen ......................... 195 Figure 116. Configuration Options Screen ....................... 196 Figure 117. Energy Advantage Architecture (EAA) Screen................... 196 Figure 118. Disable ESS Screen ........................197 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 xvii...
  • Page 18 Figure 130. ISBM Section Air Filter Locations – Continuous Static Switch .............. 211 Figure 131. FI-UPM Air Filter Location ......................212 Figure 132. FI-UPM Air Filter Location ......................213 xviii Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 19 Bonding Requirements for the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/ 825............................. 35 Table 11. UPS Intercabinet Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395- 1100/1100, and the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825 ....35 Table 12.
  • Page 20 Display Function Menu Map ......................181 Table 37. RMP II Status Indicators........................ 206 Table 38. Customer Interface Connectors...................... 207 Table 39. SCM II Status Indicators and Connections..................208 Table 40. UPS Filter Sizes........................... 210 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 21 Technical Publications Feedback Form for User Manuals Eaton Product Type 9395 Document Number†*                                          Revision# Feedback Type:          Comments                    Error Report                     Questions Describe Feedback*: Suggestions:  Name* E‐mail*  Please complete the form and submit it to Eaton Technical Publications by clicking on the  following link:  Submit Completed Form † Document numbers can be found in the footer sec on or last page of the manual.    Example: “xxxxxxxxx” (nine digits)  *Required ...
  • Page 22 275 kVA for a total maximum of 1100 kVA. The Power Xpert 9395 Three UPM UPS (650-825 kVA) contains two sections: an ISBM or an IOM rated for a maximum of 1100 kVA (to provide future upgradability) and an UPM section containing three UPMs. Each UPM is rated for a maximum of 275 kVA for a total maximum of 825 kVA.
  • Page 23 The control panel, located on the front of the UPS, contains a liquid crystal display (LCD) or color touchscreen and pushbutton switches to control the operation of the UPS and to display the status of the UPS system. See Chapter 7 UPS Operating Instructions for additional information. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 24 1 1 . . 1 1 . . 5 5 P P o o w w e e r r M M a a n n a a g g e e m m e e n n t t S S o o f f t t w w a a r r e e LanSafe ® Power Management Software is bundled as part of the Software Suite CD shipped with the UPS. See Chapter 8 Communication for additional information. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 25 1 1 . . 2 2 . . 5 5 S S e e p p a a r r a a t t e e R R e e c c t t i i f f i i e e r r I I n n p p u u t t If a FI-UPM is to be installed with the Power Xpert 9395 1000–1100 kVA UPS at the initial installation or in the future, the UPS can be supplied with separate rectifier inputs for each UPM.
  • Page 26 1 1 . . 2 2 . . 9 9 I I n n h h e e r r e e n n t t R R e e d d u u n n d d a a n n c c y y To deliver greater reliability, the Power Xpert 9395 UPS can be configured by an authorized Eaton Customer Service Engineer for inherent redundancy if a FI-UPM is installed.
  • Page 27 A ConnectUPS™-X Web/SNMP Card is required in an X-Slot communication bay. An optional Environmental Monitoring Probe (EMP) is required for temperature/humidity monitoring, Chapter 8 Communication for additional information on monitoring and communication features. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 28 U U s s i i n n g g T T h h i i s s M M a a n n u u a a l l This manual describes how to install and operate the Power Xpert 9395 1000–1100 kVA UPS. Read and understand the procedures described in this manual to ensure trouble-free installation and operation.
  • Page 29 F F o o r r M M o o r r e e I I n n f f o o r r m m a a t t i i o o n n Refer to the Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual for the following additional information: •...
  • Page 30 1 1 . . 9 9 W W a a r r r r a a n n t t y y To view the UPS warranty please click on the link or copy the address to download from the Eaton website: UPS Product Warranty https://www.eaton.com/content/dam/eaton/products/backup-power-ups-surge-it-power-distribution/backup-...
  • Page 31 Introduction Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 32 ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 33 End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no upward angling. If these instructions are not followed, damage to the wiring channel and wiring will occur. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 34 Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. • Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 35 Safety Warnings Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 36 If the UPS is to be operated at an altitude higher than 1000 m (3000 ft), contact an Eaton service representative for important information about high altitude operation. The operating environment must meet the weight, clearance, and environmental requirements specified.
  • Page 37 3 3 . . 2 2 . . 3 3 I I n n s s t t a a l l l l a a t t i i o o n n C C o o n n s s i i d d e e r r a a t t i i o o n n s s The UPS system installation must meet the following guidelines: • The system must be installed on a level floor suitable for computer or electronic equipment. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 38 Figure 3 through Figure 13. Dimensions are in millimeters (inches). For Field Installed UPM (FI-UPM) weights and dimensions, refer to the Eaton 9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.7 For More Information. Table 2Includes the weights of the heaviest cabinet configuration.
  • Page 39 UPS requirements. Operating temperatures above the recommended range will result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton’s Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more information.
  • Page 40 Figure 3. UPS Cabinet Dimensions - Three UPM (Front View) Dimensions are in millimeters [inches]. Figure 4. UPS Cabinet Dimensions – Four UPM (Front View) Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 41 UPS Installation Plan and Unpacking Figure 5. UPS Cabinet Dimensions (Right Side View) [1.6] [32.7] 871.7 [34.3] Dimensions are in millimeters [inches]. Figure 6. ISBM Section Dimensions (Front View) Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 42 UPS Installation Plan and Unpacking Figure 7. UPM Section Dimensions (Front View) Dimensions are in millimeters [inches]. Figure 8. UPM Section Dimensions (Top View) Front Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 43 UPS Installation Plan and Unpacking Figure 9. ISBM Section Dimensions (Top View) Front Dimensions are in millimeters [inches]. Figure 10. ISBM Section Dimensions (Bottom View) Front Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 44 UPS Installation Plan and Unpacking Figure 11. ISBM Section Center of Gravity Dimensions are in millimeters [inches]. Figure 12. UPM Section Center of Gravity Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 45 DO NOT install both a source neutral and a bonding jumper. See Table Table Table 7, or Table 8 neutral bonding jumper wire sizes. The bonding jumper must be copper wire. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 46 UPS function and requires no additional work by the installer or user. Please contact the Eaton help desk listed in Chapter 1 for additional guidance regarding dual high impedance ground sources. When selecting the most appropriate grounding scheme for your application, consider items such as: –...
  • Page 47 Because of the future upgradability to a fully rated 1100 kVA UPS with the adc dition of the FI-UPM, the UPS wiring is specified for 1100 kVA in Table 7 Table Wire sizes listed are for copper wiring only. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 48 UPS Installation Plan and Unpacking Table 5. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000 and 9395- 1100/1100 – Common Battery Rating 50/60 Hz Units Basic Unit Rating 1000 1000 1000 1000 1001 1001 Input and Output Voltage...
  • Page 49 UPS Installation Plan and Unpacking Table 5. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000 and 9395- 1100/1100 – Common Battery (Continued) Rating 50/60 Hz Units Basic Unit Rating 1000 1000 1000 1000 1001 1001...
  • Page 50 UPS Installation Plan and Unpacking Table 6. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000, and 9395- 1100/1100 – Separate Battery Rating 50/60 Hz Units Basic Unit Rating 1000 1000 1000 1000 1001 1001 Input and Output Voltage...
  • Page 51 UPS Installation Plan and Unpacking Table 6. Input/Output Ratings and External Wiring Requirements for the Four UPM Power Xpert 9395-1100/1000, and 9395- 1100/1100 – Separate Battery (Continued) Rating 50/60 Hz Units Basic Unit Rating 1000 1000 1000 1000 1001 1001...
  • Page 52 UPS Installation Plan and Unpacking Table 7. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395- 1100/750, and 9395-1100/825 – Common Battery Rating 50/60 Hz Units Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480 AC Input to UPS Rectifier (0.98 Minimum pF)
  • Page 53 UPS Installation Plan and Unpacking Table 7. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395- 1100/750, and 9395-1100/825 – Common Battery (Continued) Rating 50/60 Hz Units Basic Unit Rating Input and Output Voltage Volts...
  • Page 54 UPS Installation Plan and Unpacking Table 8. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395- 1100/750, and 9395-1100/825 – Separate Battery Rating 50/60 Hz Units Basic Unit Rating Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480 AC Input to UPS Rectifier (0.98 Minimum pF)
  • Page 55 UPS Installation Plan and Unpacking Table 8. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-1100/650, 9395- 1100/750, and 9395-1100/825 – Separate Battery (Continued) Rating 50/60 Hz Units Basic Unit Rating Input and Output Voltage Volts...
  • Page 56 AWG or kcmil Minimum Conductor Size (each) Number per Phase Table 11. UPS Intercabinet Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100, and the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825 Tightening Bus Landings Terminal Function...
  • Page 57 Figure 36 show the location of the power cable terminals inside the UPS. Table 13. UPS External Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100, and the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825 Tightening Torque...
  • Page 58 UPS Installation Plan and Unpacking Table 13. UPS External Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100, and the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825 (Continued) Tightening Torque Bolt Bus Landings Terminal Function Terminal...
  • Page 59 Table 8 for wiring requirements. If an output lockable disconnect is required, it is to be supplied by the customer. Table 17 lists the recommended rating for input circuit breakers. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 60 NOTE 1 Because of the future upgradability to a fully rated 1100 kVA UPS with the addition of the FI-UPM, these breaker sizes are specified for an 1100 kVA UPS. NOTE 2 Bypass breakers are not required for IOM configurations. There is no manual DC disconnect device within the UPS. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 61 Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. Read and understand the following notes while planning and performing the installation: Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 62 HIGH ALERT mode is desired because any loads with a leading power factor will not be seen by the generator. Rectifier operation will be much softer while on generator thereby increasing overall system stability Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 63 UPS function and requires no additional work by the installer or user. Please contact the Eaton help desk listed in Chapter 1 for additional guidance regarding dual high impedance ground sources. When selecting the most appropriate grounding scheme for your application, consider items such as: –...
  • Page 64 If these instructions are not followed, damage to the wiring channel and wiring will occur. Carefully inspect the outer packaging for evidence of damage during transit. Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service representative immediately.
  • Page 65 Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading. If damage has occurred or shortages are evident, contact an Eaton service representative immediately to determine the extent of the damage and its impact on further installation.
  • Page 66 UPS Installation Plan and Unpacking Figure 14. UPS Cabinet as Shipped on Pallet (ISBM Section) Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 67 UPS Installation Plan and Unpacking Figure 15. UPS Cabinet as Shipped on Pallet (UPM Section) Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 68 If these instructions are not followed, damage to the wiring channel and wiring will occur. NOTE For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 2) for cabinet weight). Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 69 19). Remove the right side shipping bracket. Figure 16. Removing the ISBM Section Left Side Shipping Bracket Front Door Pallet Shipping Bracket Bolts Shipping Bracket Left Side Shipping Bolts Bracket Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 70 Carefully lower the UPS cabinet until the cabinet base contacts the floor. Repeat Steps 2 through 6 for the remaining cabinet. Proceed to paragraph 4.3 Mechanically Joining the Sections. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 71 UPS System Installation Figure 18. Removing the UPM Section Left Side Shipping Bracket UPM Removable Front Panels Pallet Shipping Bracket Bolts Wireway Panel Shipping Bracket Left Side Shipping Bolts Bracket Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 72 Lift the panel straight up to remove it from the panel hanger brackets at the top of the cabinet. Remove the screws securing the top and bottom internal safety shield panels and remove the panels. Retain the hardware for later use. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 73 UPM section from damage. NOTE Clearance between the ISBM and the UPM sections must be less than 1/2” so that joining brackets can be installed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 74 ISBM and UPM sections. Secure the bracket with the screws from the hardware kit (see Figure 22). 13. Proceed to paragraph 4.4 Electrically Connecting the Sections. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 75 ISBM section to the AC Input to UPMs terminals. See Figure 23 for common rectifier feed with Continuous Static Switch (CSS) terminal locations. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 76 Figure 24). This hardware is used by an Eaton Customer Service Engineer to install a Field Installed UPM (FI-UPM). 13. Locate the ground braid in the bottom left front corner of the UPM section. The ground braid is secured at the factory to the UPM section ground bolt.
  • Page 77 27. If installing a tie cabinet or distribution panel for a distributed bypass system, proceed to paragraph 4.7 Distributed Bypass Tie Cabinet Installation; otherwise, proceed to paragraph 4.8 Installing UPS External and Battery Power Wiring. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 78 NOTE On a UPS configured with a Continuous Static Switch (CSS), CB4 is not installed. NOTE On a UPS configured as an Input Output Module (IOM), CB4 is not installed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 79 NOTE On a UPS without CB1, UPM input wiring terminations are in the same positions on the bus bars installed in the place of CB1. NOTE On a UPS configured as an IOM, UPM input wiring terminations are the same as an ISBM configuration. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 80 DC Input to UPMs Cable 2G3 Red Cable 2G3 Black Cable 3G3 Black Cable 3G3 Red – UPM 3 (3E4A) UPM 3 (3E5A) Cable 3G3 Black Cable 3G3 Red Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 81 NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 82 Location of P61 Harness Front Front UPM Wireway Location of P50, P51, and P70 Harnesses Location of RJ-45 Coiled CAN Cable ISBM Section Right Side View UPM Section Left Side View Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 83 UPS System Installation Figure 28. Pl1 Interface Board Location Pl1 Interface Board Front ISBM Section Right Side Inside View Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 84 NOTE FI-UPM installation is not applicable to a three UPM model. If installing a four UPM model, install the FI-UPM using the instructions in the Power Xpert 9395 Field Installed UPM Mechanical Installation Manual, listed in paragraph 1.7 For More Information.
  • Page 85 Drill and punch all conduit holes in the bottom conduit plate prior to mounting on the UPS. Install the conduit plate and install all conduit runs into the plate. Pull the wiring through conduit into the wiring area. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 86 Figure 30. ISBM and UPM Section Debris Shields Ventilation Grill Debris Shield (Remove shield before operating system.) ISBM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) UPM Section Front Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 87 Using hardware from the external wiring terminal hardware kit (see Table 14), connect phase A, B, and C, and Neutral (if required) bypass input power wiring from the utility source to the bypass input terminals and Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 88 Neutral (if required) power wiring from output terminals and neutral terminals to the critical load. See paragraph 3.2.4 UPS System Power Wiring Preparationfor wiring and termination requirements. 12. Proceed to paragraph 4.8.2 Battery Power Wiring. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 89 NOTE Any difference in wire length will result in decreased capacity of the UPS system while on bypass. For example, a 10% difference between the longest and shortest wire lengths will result in a decrease in bypass capacity of 10%. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 90 **See Figure ”ISBM Section Power Terminal Detail BB” – ("Common Battery” or “Separate Battery”) as applicable for Detail ISBM NOTE AC Input to Bypass terminals are not applicable to an IOM configuration. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 91 When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10 Product Specifications for maximum battery charger currents. To install wiring to connections: NOTE An installed FI-UPM is always designated as UPM 4. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 92 Installation, Step 2. Secure with the retained hardware. Reinstall the left front panel removed in paragraph 4.8.1 External Power Wiring Installation, Step 1 and secure with the retained hardware. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 93 UPS System Installation Figure 35. ISBM Section Power Terminal Detail BB – Common Battery DC Input from Battery + (E4) Front DC Input from Battery – (E5) Section B–B Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 94 Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. Use the procedures in the following paragraphs to connect the TB1, TB1 Battery, TB2, and TB3 interface connections. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 95 10. Reinstall the top internal safety shield panel and secure with the retained hardware. 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 96 UPS System Installation Figure 37. ISBM Section Interface Terminal Locations ISBM Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 97 Default function set for charger off. Building Alarm 3 Return Input: Programmable UPS alarm, activated by a remote dry contact closure. Building Alarm 4 Default function set for on generator. Default: On Generator Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 98 NOTE “Return” indicates connection to electronics circuit ground. “Common” indicates connection to common side of isolated relay contact. Figure 38. Interface Terminal Detail X-Slot Communication Bays See Figure ”Terminal Blocks TB1, TB2, and TB3 Connector Assignments” for terminal assignments. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 99 NOTE Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is required. NOTE Alarm relay wiring should be a minimum of 22 AWG Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 100: Figure 40. Terminal Blocks Tb1, Tb2, And Tb3 Connector Assignments

    NOTE The building alarms can be programmed to display the alarm functional name. NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed REPO contact is not used. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 101 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. If wiring X-Slot connections, proceed to paragraph 4.9.3 X-Slot Connections; otherwise, proceed to Step 13. Close the door and secure the latch. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 102: Figure 41. Typical Battery Interface Connection - Common Battery System

    When installing external wiring to X-Slot cards, conduit must be installed to the UPS cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the internal opening in the X-Slot communication bay. For installation and setup of an X-Slot card, contact an Eaton service representative (see 1.8 Getting Help).
  • Page 103: Figure 43. X-Slot Communication Bays

    4.2 Unloading the UPS Cabinet from the Pallet through 4.9 Installing Interface Connections. NOTE When installing the REPO switch, you must install conduit between the device and the UPS cabinet for wiring the switch. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 104: Figure 44. Repo Switch

    The REPO switch must be a normally-open or normally-closed latching–type switch not tied into any other circuits. NOTE This procedure is intended to be used for the installation of the Eaton-supplied REPO switch. If installing another manufacturer's switch, use this procedure only as a guide. NOTE The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
  • Page 105: Figure 45. Normally-Open Repo Switch Wiring

    Figure 47 shows the wiring connections if the normally-closed REPO contacts are used, and Figure 47 shows alternative methods of connecting a REPO switch if using another manufacturer's switch. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 106: Figure 46. Normally Closed Repo Switch Wiring

    REPO switch must be a latching-type switch not tied to any other circuits. NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 107 (see Section Warranty). This service is offered as part of the sales contract for the UPS system. Contact an Eaton service representative in advance (usually a two-week notice is required) to reserve a preferred startup date.
  • Page 108 Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (OPTIONAL) o The debris shield covering the UPS cabinet ventilation grill is removed. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 109 Pull-chain wiring between the UPS cabinets is properly installed. o Adequate workspace exists around the UPS cabinets, the tie cabinet, and other cabinets. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 110 UPS System Installation Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 111 UPS System Installation Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 112 In addition, this card can be used to connect optional system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface Module II, or a Supervisory Contact Module II to the UPS. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 113: Figure 48. Powerware Hot Sync Can Bridge Card

    UPS. See Figure 27 Figure 33 for X-Slot communication bay locations. To locate the appropriate terminals on the Powerware Hot Sync CAN Bridge Card, see Figure 49 Table Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 114: Figure 49. Powerware Hot Sync Can Bridge Card Connections

    Alarm Relay NO Normally open contact closes when UPS is on bypass. RMP II, RIM II, and SCM II connections. CAN L CAN Input for parallel operation. Can H Shield Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 115 NOTE Setup of the Powerware Hot Sync CAN Bridge Card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 12. Reinstall the small top internal safety shield panel and secure with the cabinet mounted screws.
  • Page 116: Figure 50. Distributed Bypass System Can And Pull-Chain Simplified Interface Wiring

    CAN Bridge Card J3 CAN Bridge Card J3 CAN Bridge Card J3 CAN Bridge Card J3 (If Installed) (If Installed) NOTE External CAN connections between UPSs require shielded twisted-pair wire. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 117: Figure 52. Distributed Bypass Pull-Chain Wiring Without Mobs

    Twisted Pair Twisted Pair Twisted Pair UPS 1 UPS 2 UPS 3 UPS 4 (If Installed) (If Installed) NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 118 To UPS 2 TB2–1 TB2–1 TB2–1 TB2–1 (Pull Chain) (Pull Chain) (Pull Chain) (Pull Chain) TB2–2 TB2–2 TB2–2 TB2–2 (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) (Pull Chain Common) Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 119: Figure 53. Distributed Bypass Pull-Chain Wiring With Mobs

    NOTE External CAN connections between UPS cabinets require shielded twisted-pair wire. NOTE Use twisted-pair wiring between the UPS and MOB AUX contacts. NOTE Always confirm contact operation prior to wiring. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 120 Securely mount the RMP II at the desired location. See Figure 59 for mounting hole locations. NOTE When installing signal wiring for CAN card J3 terminals, conduit must be installed between the device and the UPS cabinet. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 121: Figure 54. Remote Monitor Panel Ii And Remote Monitor Panel Ii Terminal Locations

    Figure 54. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations Ground Terminal Terminal TB1 Signal Connections from the UPS Terminal TB3 120 Vac Power Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 122: Figure 55. Remote Monitor Panel Ii, Relay Interface Module Ii, Or Supervisory Contact Module Ii Wiring

    If a fuse replacement does not correct the problem, contact an Eaton service representative for verification that the RMP II is working correctly. 12. To test the indicator lamps, press and hold the horn silence pushbutton for three seconds. All lamps should illuminate, and the horn sounds continuously until you release the pushbutton.
  • Page 123 Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. Contact an Eaton service representative for verification and testing of the RIM II and its connections prior to making connections with J1 through J4 (see...
  • Page 124: Figure 56. Figure 5-9J1, J2, J3, And J4 15-Pin D-Sub Connectors

    120 Vac for the SCM II should be supplied from the critical bus by facility planners or the customer. Install 120 Vac power wiring from the critical bus to the SCM II. See Figure Figure 55, and Table 27 the terminal location and wiring information. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 125: Figure 57. Supervisory Contact Module Ii Terminal Location

    Figure 58 for terminal assignments. 10. Close the front door and secure the latch. 11. Restart the UPS. See Chapter 7 UPS Operating Instructions for startup instructions. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 126: Figure 58. Supervisory Contact Module Ii Tb2

    Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc. NOTE Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of supplying contact current. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 127: Figure 59. Remote Monitor Panel Ii Dimensions

    Flush Mount using #10 Pan Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 128: Figure 60. Relay Interface Module Ii Dimensions

    Flush Mount using #10 Pan Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 129: Figure 61. Supervisory Contact Module Ii Dimensions

    Flush Mount using #10 Pan Head Screws. (Mount with vent holes facing up.) Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Dimensions are in millimeters [inches]. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 130: Figure 62. Main Elements Of The Ups System

    U U P P S S S S y y s s t t e e m m O O v v e e r r v v i i e e w w The Eaton 9395 UPS is a continuous-duty, solid–state, transformerless (at 480 Vac), three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load.
  • Page 131 6 6 . . 2 2 . . 1 1 M M o o d d e e s s The Eaton 9395 UPS supports a critical load in five different modes of operation: NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.
  • Page 132: Figure 63. Path Of Current Through The Ups In Online Mode

    Some power line filtering and spike protection is provided to the load but no active power conditioning or battery support is available. All power converters are off and are in the ready state Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 133 UPM full power rating. If the limit is exceeded, additional UPMs take on the increased load. The VMMS redundancy setting sets the number of redundant UPMs that the customer requires. Both the VMMS UPM load limit and UPM redundancy are customer configurable. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 134 K3 opens to isolate the inverter. The backfeed protection contactor is normally closed, ready to support the static switch unless the bypass input source becomes unavailable. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 135: Figure 64. Path Of Current Through The Ups In Bypass Mode

    In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. Figure 65 shows the path of electrical power through the UPS system when operating in Battery mode. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 136: Figure 65. Path Of Current Through The Ups In Battery Mode

    NOTE On a UPS configured as an IOM, the bypass input, static switch, bypass breaker (CB4), and K5 are not present. NOTE On a UPS configured with a Continuous Static Switch (CSS), bypass breaker (CB4) is not present. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 137 Single Reverse Transfer UPS – Four UPM, 9395-1100/1000 Figure 71 Common Rectifier Feed, Separate Battery, IOM 9395-1100/1100 Configuration 9395-1100/650 9395-1100/750 Simplified Dual-Fed UPS with Maintenance Figure 72 9395-1100/825 Bypass Panel 9395-1100/1000 9395-1100/1100 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 138: Figure 66. Ups System - Four Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration, Continuous Static Switch

    Input/Output Ratings and External Wiring Requirements (Four UPM, Common Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 139: Figure 67. Ups System - Four Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration

    Input/Output Ratings and External Wiring Requirements (Four UPM, Separate Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 140: Figure 68. Ups System - Three Upm, Common Rectifier Feed, Common Battery, Dual-Feed Configuration

    Input/Output Ratings and External Wiring Requirements (Three UPM, Separate Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 141: Figure 69. Ups System - Three Upm, Common Rectifier Feed, Separate Battery, Dual-Feed Configuration

    Input/Output Ratings and External Wiring Requirements (Three UPM, Separate Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 142: Figure 70. Ups System - Four Upm Common Rectifier Feed, Common Battery, Iom Configuration

    Input/Output Ratings and External Wiring Requirements (Four UPM, Common Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 143: Figure 71. Ups System - Four Upm Common Rectifier Feed, Separate Battery, Iom Configuration

    Input/Output Ratings and External Wiring Requirements (Four UPM, Separate Battery) Table in Chapter 3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 144: Figure 72. Simplified Dual-Feed Ups With Maintenance Bypass Panel

    (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is acceptable for supplying both the UPS and the bypass. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 145 6 6 . . 4 4 . . 1 1 M M u u l l t t i i p p l l e e U U P P S S P P a a r r a a l l l l e e l l S S y y s s t t e e m m M M o o d d e e s s Similar to the single UPS system, the Eaton 9395 UPS parallel system supports a critical load in five different modes of operation.
  • Page 146 If the UPSs become overloaded or unavailable, the distributed bypass system switches to Bypass mode. The distributed bypass system automatically returns to Online mode when the overload condition is cleared and system operation is restored within specified limits. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 147: Figure 73. Path Of Current Through The Upss In Online Mode - Distributed Bypass

    If more modules than can support the load must be taken offline, the load must be transferred to maintenance bypass or shut down. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 148: Figure 74. Path Of Current Through The Upss In Bypass Mode - Distributed Bypass

    In the Parallel Capacity (N+0) arrangement, if one UPS trips offline and goes to bypass, the remaining UPSs also go to bypass. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 149: Figure 75. Path Of Current Through The Upss In Battery Mode - Distributed Bypass

    Battery UPS 2 Output UPS 2 Battery UPS 3 Output UPS 3 Battery UPS 4 Output UPS 4 Battery Breakers Closed Output to Main Power Flow Critical Load Open Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 150 9395-1100/1100 Multiple UPS – Distributed Bypass 2+1 and 3+0 9395-1100/650 Configurations 9395-1100/750 9395-1100/825 Figure 78 9395-1100/1000 Multiple UPS – Distributed Bypass 3+1 and 4+0 9395-1100/1100 Configurations 9395-1100/650 9395-1100/750 9395-1100/825 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 151: Figure 76. Typical Distributed Bypass System (1+1 And 2+0 Configurations)

    UPS is shown in the Single UPS System Oneline Configurations Section 6.3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 152: Figure 77. Typical Distributed Bypass System (2+1 And 3+0 Configurations)

    UPS is shown in the Single UPS System Oneline Configurations Section 6.3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 153: Figure 78. Typical Distributed Bypass System (3+1 And 4+0 Configurations)

    UPS is shown in the Single UPS System Oneline Configurations Section 6.3. NOTE If the load requires a neutral, a bypass source neutral must be provided. DO NOT install both a source neutral and a bonding jumper. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 154: Figure 79. Ups Controls And Indicators - Continuous Static Switch

    The controls and indicators identified and described in this section are used to control and monitor UPS operation. Figure 79 shows the controls and indicators. Figure 79. UPS Controls and Indicators – Continuous Static Switch Pushbutton Control Panel AC Input Breaker CB1 (optional) ISBM Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 155: Figure 80. Ups Control Panel

    Figure 80. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once. When the unit powers up, the screen displays the Eaton logo as shown in Figure 80. To advance to the Main Menu and Mimic screen, press any control panel pushbutton once.
  • Page 156 Figure 81 identifies the display areas discussed in the following sections. Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual 164201603 Rev 4 8-41 Eaton 9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual...
  • Page 157: Figure 81. Parts Of The Lcd

    CONTROLS LOAD OFF A The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, active notices, and load percent and battery runtime for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The top line of display blinks while scrolling when the system needs attention.
  • Page 158: Figure 82. Main Menu And Mimic Screen (Online Mode)

    164201725 Rev 4P Draft 31-Jan-2010 EATON 9395 UPS (650–825 kVA) Installation and Operation Manual 164201725 Rev 4P Draft 31-Jan-2010 EATON 9395 UPS (650–825 kVA) Installation and Operation Manual 164201725 Rev 4P Draft 31-Jan-2010 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 159 The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of battery time remaining, and battery temperature. Battery temperature must be set up by an authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%, Check Battery is displayed.
  • Page 160 System Setup screen to display the High Alert Timer screen. Use the up or down arrow pushbutton to set the time. Press SAVE or ABORT. Once the action is completed, the Energy Saver System Setup screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 161 Event and History Logs. Use the left or right arrow pushbutton to highlight the setting to be changed. Use the up or down arrow Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 162 OFF process to be aborted if the LOAD OFF pushbutton was pressed accidentally. For Load Off procedures, see paragraph 7.3.24 Using the UPS LOAD OFF Pushbutton or Command or paragraph 7.4.27 Using the UPS LOAD OFF Pushbutton or Command. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 163: Figure 83. Load Off Screen

    UPM: OFFLINE UPM: OFFLINE CONTROLS CONTROLS Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14 Figure 7-7. Typical System Status Screen Figure 7-7. Typical System Status Screen Table 7-4. Typical System Status Messages Table 7-4. Typical System Status Messages...
  • Page 164 Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode. Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to Disable when the Energy Saver System mode is enabled. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 165 *Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see Figure 79). *Verify that input breaker CB1 is open. Close the UPS input feeder circuit breaker. Close the UPS Bypass input feeder circuit breaker. *Close input breaker CB1. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 166 Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is displayed. On the UPS Control Command screen, select ENABLE ENERGY SAVER. Press the SELECT pushbutton on the UPS Command menu bar. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 167 7 7 . . 3 3 . . 5 5 E E n n a a b b l l e e V V a a r r i i a a b b l l e e M M o o d d u u l l e e M M a a n n a a g g e e m m e e n n t t S S y y s s t t e e m m M M o o d d e e f f r r o o m m t t h h e e U U P P S S C C o o m m m m a a n n d d M M e e n n u u To enable Variable Module Management System mode: Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 168 The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module Management System mode commands will not be displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 169 7 7 . . 3 3 . . 9 9 E E n n a a b b l l e e E E n n e e r r g g y y S S a a v v e e r r S S y y s s t t e e m m M M o o d d e e f f r r o o m m t t h h e e B B y y p p a a s s s s C C o o m m m m a a n n d d M M e e n n u u To enable Energy Saver System mode: Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 170 The Variable Module Management System and Energy Saver System modes are mutually exclusive. If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will not be displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 171 Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the BYPASS command. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 172 Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, the UPS status should indicate SHUTDOWN and the UPM status should indicate OFFLINE. 10. Verify no alarms are active. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 173 *Only perform steps 2 and 5 if the UPS has an input breaker CB1 (see Figure 79). *Verify that input breaker CB1 is open. Close the UPS input feeder circuit breaker. Close the UPS Bypass input feeder circuit breaker. *Close input breaker CB1. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 174 Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the BYPASS command. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 175 Press the CONTROLS pushbutton on the System Status Command menu bar. The UPM 1 Control Command screen is displayed. 10. On the UPM 1 Control Command screen, select UPM OFF. 11. Press the SELECT pushbutton on the UPM 1 Command menu bar. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 176 7 7 . . 3 3 . . 2 2 1 1 S S i i n n g g l l e e U U P P M M R R e e s s t t a a r r t t To restart a single UPM from a shutdown state: Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 177 To turn the battery charger on: Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the CHARGER command. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 178 Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. To use the LOAD OFF command: Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 179 NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 180: Figure 85. Repo Operation

    Close all UPS input feeder circuit breakers. Close all UPS Bypass input feeder circuit breakers. If the UPSs contain input breakers (CB1), close all input breakers. Close the doors and secure the latches. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 181 On the UPS Control Command screen, select ENABLE ENERGY SAVER. Press the SELECT pushbutton on the UPS Command menu bar. The UPS transfers to Energy Saver System mode. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 182 To enable Variable Module Management System mode: NOTE The Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 183 Management System mode commands will not be displayed. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the UPS command. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 184 7 7 . . 4 4 . . 9 9 E E n n a a b b l l e e E E n n e e r r g g y y S S a a v v e e r r S S y y s s t t e e m m M M o o d d e e f f r r o o m m t t h h e e B B y y p p a a s s s s C C o o m m m m a a n n d d M M e e n n u u To enable Energy Saver System mode: NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by an Eaton Customer Service Engineer. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 185 Energy Saver System mode commands will not be displayed. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. On the System Status screen, select the BYPASS command. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 186 Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen is displayed. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT. Press the SELECT pushbutton on the Bypass Command menu bar. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 187 12. On the System Status screen, select the UPM command. The UPS Control Command screen is displayed. 13. On the UPS Control Command screen, select the UPM 1 command. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 188 Close the door and secure the latch. Observe the UPS control panel becoming active, indicating logic power. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 189 All of the UPSs transfer to Bypass mode and the critical load is immediately supplied by the bypass source. If the bypass source is not available, the power module remains on and an alarm sounds. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 190 12. To turn off the power module, press the CONTROLS pushbutton on the UPS Control Command menu bar. The UPM 1 Control Command screen is displayed. 13. On the UPM 1 Control Command screen, select UPM OFF. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 191 On the UPS Control Command screen, select the UPM to restart. Press the CONTROLS pushbutton on the UPS Control Command menu bar. The UPM Control Command screen is displayed. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 192 UPS being shut down. Logic power remains on. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 193 15. Press the SELECT pushbutton on the UPM 1 Command menu bar. The UPM status indicates SHUTDOWN. The input, output, and battery contactors open, and the power module is turned off. Logic power remains on. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 194 The UPS will start, sync to the other UPSs online, and go online. 16. Verify the following messages display sequentially on the UPM status line:DC STARTING, CHARGER OFF INVERTER STARTING INVERTER SYNCING ONLINE, CHARGER ON Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 195 UPS Control Command screen, or the Load Off command on the Bypass Control Command screen. The UPS LOAD OFF controls the UPSs' outputs by powering down the UPS and de–energizing the critical load. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 196 All power to the critical load is lost when LOAD OFF is selected in the following step. You should use this feature only when you want to de–energize the critical load. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 197 NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer- supplied REPO switch is used, it may not activate in the same manner; refer to the operating instructions provided with the switch.
  • Page 198: Figure 86. Ups Color Touchscreen Control Panel (Typical)

    For a description of the UPS control panel functions, see paragraph 7.6 Using the Color Touchscreen Control Panel. Figure 86. UPS Color Touchscreen Control Panel (Typical) Color Touchscreen Control Panel ISBM Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 199: Figure 87. Ups Color Touchscreen Control Panel Screen And Indicators(Typical)

    The symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to let you know the operating status of the UPS. See Table Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 200 Touching anywhere on the screen brings up the Sign In Request pop-up. Touch the X in the upper right corner of the pop-up, then touch the padlock symbol in the upper right corner to obtain the password request pop-up (see Figure 89). Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 201: Figure 88. Parts Of The Touch Screen

    The UPS status area automatically displays the Eaton model number, current time and date, active alarms, active notices, and load percent and battery run time for the UPS. If the Eaton Environmental Monitoring Probe is installed, the temperature and humidity sensed by the probe will also be displayed. The small head symbol between the system model and time allows the operator select a different language from an imbedded list.
  • Page 202: Figure 89. Sign In Or Password Request Screen

    Displays performance meters for the system or critical load. CONTROLS Allows access to various system performance control screens. POWER MAPS Allows operator to observe system power flow. LOGS Allows access to system information logs. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 203: Figure 90. Home Screen

    Main Menu and Power Maps screen. The Power Maps screen displays immediately after entering the access code. The Power Maps screen shows a real-time graphical representation of the operating status. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 204: Figure 91. Main Menu And Power Maps Screen (Online Mode)

    Touching the LOAD kVA button displays the Output kVA screen shown in Figure Figure 92. Output kVA Screen from Home Screen Touching the AVERAGE EFFICIENCY button displays the system efficiency screen shown in Figure Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 205: Figure 93. Average Efficiency Screen From Home Screen

    Figure 95 shows the Bypass screen. The Bypass screen displays only when the system is in Bypass mode. The Bypass screen shows a real-time graphical representation of the operating status. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 206: Figure 95. Bypass Screen

    24 hours, 7 days, 30 days, or 1 year. This is true of all the meters screens listed in the top section. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 207: Figure 97. Meters Summary Screen

    Input Meters screen. This screen displays the individual phase and total power values of the system. Figure 98. Input Meters Screen The Bypass Meters Screen shown in Figure 99 displays values pertaining to the Bypass conditions. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 208: Figure 99. Bypass Screen

    7 7 . . 6 6 . . 9 9 I I n n p p u u t t M M e e t t e e r r s s D D e e t t a a i i l l S S c c r r e e e e n n Figure 101 shows the Input Meters detail screen. This screen displays the individual values of the system in additional detail. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 209: Figure 101. Input Meters Detail Screen

    Figure 101. Input Meters Detail Screen The Select Source screen shown in Figure 102 allows the operator to choose the individual source for system readings. Figure 102. Select Source Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 210: Figure 103. Battery Meters Screen

    Battery Meters basic screen. Figure 103. Battery Meters Screen Figure 104 shows the Battery Log access screen. Figure 104. Battery Log Screen Figure 105 shows the Battery Log Detail screen. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 211: Figure 105. Battery Log Detail

    In Battery or Bypass modes, the UPS may issue alarms to display exactly what event caused the change from Online mode. System events on the UPS can be indicated by horns, lights, messages, or all three. See Figure 107. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 212: Figure 107. System Events Screen

    The operator can also use the UP/DOWN arrows above and below the blue field (2) showing the number of events in the log. See Figure 108. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 213: Figure 108. User Log Screen

    UPM start up and shutdown, and LOAD OFF commands are controlled through this screen. In addition, the screen displays the current status of the UPS, indicates whether the UPS is in Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 214: Figure 110. System Status Screen

    Figure 111 shows the Module Controls screen. This screen allows control of the individual modules within the system. It also gives their values and status. Figure 111. Module Controls Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 215: Figure 112. Module Control Detail Screen

    Figure 112. Module Control Detail Screen The Metering Method screen allows the operator to select line-to-line or line-to-neutral monitoring values. See Figure 113 Figure 114. Figure 113. Online Mode Metering Method Option Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 216: Figure 114. Bypass Mode Metering Method Option Screen

    Touching the CLEAN SCREEN button disables the screen for 30 seconds to allow the user to safely clean the screen without affecting operation. Figure 115. Settings Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 217: Figure 116. Configuration Options Screen

    The various Energy Advantage Architecture operations are described in the UPS Installation and Operation manual for your system. Figure 117. Energy Advantage Architecture (EAA) Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 218: Figure 118. Disable Ess Screen

    HRS metering values. Figure 119. HRS Metering Screen This screen shown in Figure 120 asks the operator if they want to start the High Alert mode timer. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 219: Figure 120. High Alert Timer Screen

    7 7 . . 6 6 . . 1 1 7 7 S S t t a a t t i i s s t t i i c c s s B B a a s s i i c c S S c c r r e e e e n n The screen shown in Figure 121 allows the operator to query the system for various operational statistics such as shown in Figure 122. Figure 121. Statistics Basic Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 220: Figure 122. Statistics Data Detail Screen

    7 7 . . 6 6 . . 1 1 9 9 U U P P S S M M o o d d u u l l e e M M a a p p S S c c r r e e e e n n The screen shown Figure 124 allows the operator to control the individual UPMs. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 221: Figure 124. Ups Module Map Screen

    7 7 . . 6 6 . . 2 2 0 0 S S y y s s t t e e m m O O v v e e r r v v i i e e w w S S c c r r e e e e n n The screen shown Figure 125 displays values for all UPS and UPM parameters. Figure 125. System Overview Screen Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 222 The Online status indicator is illuminated. The UPS status indicates ONLINE on the header section of the screen. The UPM status indicates ONLINE, CHARGING on the MIMIC Screen. To activate or enable/disable any of the UPS operational modes, follow the online screen prompts. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 223 To obtain any system information, follow the on screen prompts to get to the proper screen. The operator cannot inadvertently cause a system dump or disconnect unless they override a warning pop-up. Value or information screens DO NOT affect system operation. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 224: Figure 126. Optional X-Slot Cards

    C C h h a a p p t t e e r r 8 8 C C o o m m m m u u n n i i c c a a t t i i o o n n This chapter describes the communication features of the Power Xpert 9395 UPS and provides information about connecting hardware and using Terminal mode.
  • Page 225 The eNotify Service runs on common protocols and transport mechanisms, making the connectivity between the Power Xpert 9395 UPS and the Eaton Remote Monitoring servers easy to set up. By using common e-mail transport mechanism, you do not have to open your network to proprietary or potentially unsecure protocols and transports.
  • Page 226: Figure 127. Remote Monitor Panel Ii

    The software’s mass configuration capabilities make installation and maintenance easy, which minimizes the effort required and benefits the bottom line. Eaton’s cost-effective Intelligent Power Software manages up to ten devices at no charge, with licences for up to 100 devices – or even an unlimited number – also available.
  • Page 227: Table 37. Rmp Ii Status Indicators

    The module uses a serial interface line and may support up to eight critical loads. The RIM II can be flush–mounted or surface–mounted on a desktop, or secured to a wall. Figure 128 shows the RIM II with its four 15–pin connectors labeled J1 through J4. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 228: Figure 128. Relay Interface Module Ii

    UPS system equipment. The SCM II can be flush–mounted or surface–mounted on a desktop, or secured to a wall. Figure 129 shows the SCM II. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 229: Figure 129. Supervisory Contact Module Ii

    TB2–7 through TB2–9 BYPASS NOT TB2–10 through TB2–12 AVAILABLE ON BATTERY TB2–13 through TB2–15 UPS ALARM TB2–16 through TB2–18 ON BYPASS TB2–19 through TB2–21 SHUTDOWN TB2–22 through TB2–24 IMMINENT Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 230 THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING. If you suspect that a battery string needs service, contact an Eaton service representative. If the string requires service, refer to the battery manufacturer's operating manual for instructions on battery maintenance or contact an Eaton service representative.
  • Page 231: Table 40. Ups Filter Sizes

    Ensure the UPS is in Online mode (Online status indicator is illuminated). If an alarm lamp is illuminated or the Online status indicator is not illuminated, contact an Eaton service representative. 9 9 . . 2 2 . . 2 2 M M O O N N T T H H L L Y Y M M a a i i n n t t e e n n a a n n c c e e...
  • Page 232: Figure 130. Isbm Section Air Filter Locations - Continuous Static Switch

    If opened, close the front door and secure the latch. Figure 130. ISBM Section Air Filter Locations – Continuous Static Switch Middle Right ISBM Air Filter Bottom Left ISBM Air Filters Bottom Right ISBM Air Filters Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 233: Figure 131. Fi-Upm Air Filter Location

    The FI-UPM filter size is 20" x 44" x 0.25". Contact an Eaton service representative for a replacement filter. To remove the filter: Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton 9395 Field Installed UPM Mechanical Installation Manual listed in para 1.7 For More...
  • Page 234: Figure 132. Fi-Upm Air Filter Location

    9 9 . . 2 2 . . 4 4 A A N N N N U U A A L L M M a a i i n n t t e e n n a a n n c c e e Annual preventive maintenance should be performed only by authorized service personnel familiar with maintenance and servicing of the UPS system. Contact an Eaton service representative for more information about service offerings.
  • Page 235 M M a a i i n n t t e e n n a a n n c c e e T T r r a a i i n n i i n n g g A basic training course, available from Eaton Corporation, gives you a competent working knowledge of the UPS system operation and teaches you how to perform first level corrective maintenance.
  • Page 236 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4 Battery Voltage 480 Vdc Battery Charging Capacity Configurable per UPM at nominal line voltage: Up to 120A Battery Shunt Trip 48 Vdc Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 237 Meets FCC Regulation 47, Part 15, for class A devices Electrostatic Discharge (ESD) Immunity Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage and with no disturbance or adverse effect to the critical load. Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 238 Product Specifications Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14...
  • Page 239 16420176414 164201764 14...