UPS System Installation
Figure 46. Normally Closed REPO Switch Wiring
REPO
Switch
(NC)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
T
NOTE
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.
Figure 47. Normally Closed and Normally Open REPO Switch Wiring
REPO
Switch
(NC)
REPO
Switch
(NO)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.
90
Eaton
®
1
Twisted
Wires
2
Twisted
Wires
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)