Table 13. UPS External Power Cable Terminations for the Four UPM Power Xpert 9395-1100/1000 and 9395-1100/1100, and
the Three UPM Power Xpert 9395-1100/650, 9395-1100/750, and 9395-1100/825 (Continued)
Terminal Function
Terminal
Customer Ground
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
NOTE Bypass terminations are not applicable to IOM configurations.
Table 14. Supplied External Wiring Terminal Hardware Kit
Part
Size
Bolt, Grade 5
M10 x 25 mm
Bolt, Grade 5
M12 x 50 mm
M12
Flat Washer
M12
Flat Washer
M10
Conical Washer
M12
Conical Washer
M12
Nut
NOTE Bypass terminations are not applicable to IOM configurations.
Table 15. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part
Long Barrel 2-Hole Lug
Manual Hydraulic Crimp Tool
Die Set
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground
must be run in the same conduit as the phase conductors.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
Function
Ground
Ground
Quantity
15
98
Rectifier Input, Bypass Input, Battery Input, and
15
196
Rectifier Input, Bypass Input, Battery Input, and
15
Rectifier Input, Bypass Input, Battery Input, and
98
Rectifier Input, Bypass Input, Battery Input, and
98
Quantity
Size
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
As required
300 MCM
350 MCM
400 MCM
500 MCM
14 Ton
1
N/A
1
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
UPS Installation Plan and Unpacking
Bus Landings
15 – 1 bolt mounting
Terminals Used On
Ground
Output
Ground
Output
Ground
Output
Output
Manufacturer
Part Number
Thomas & Betts
54862BE
Thomas & Betts
54864BE
Thomas & Betts
54866BE
Thomas & Betts
54868BE
Thomas & Betts
54870BE
Thomas & Betts
54872BE
Thomas & Betts
54874BE
Thomas & Betts
54876BE
Thomas & Betts
TBM14M
Thomas & Betts
15506
Tightening Torque
Bolt
Nm (lb ft)
Size
22 (16)
M10
Table
16.
Eaton Part Number
180190078-087
180190078-115
180500036-100
180500036-120
180500037-100
180500037-120
180200001-07
Notes
Copper wire only
Table 16
for conduit