Figure 4-19. Normally-Closed Repo Switch Wiring; Figure 4-20. Normally-Closed And Normally-Open Repo Switch Wiring - Eaton CA22106060000R6 Installation And Operation Manual

High performance 300 kva, 300 kw for use with single upm (200–300 kva) and plus 1 (200–300 kva) ups models
Table of Contents

Advertisement

Eaton Power Xpert 9395P UPS (300 kVA, 300 kW) Installation and Operation Manual
1
REPO
Switch
(NC)
2
NOTE REPO switch rating is 24 Vdc, 1A minimum.
T
NOTE
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.
Figure 4‐19. Normally‐Closed REPO Switch Wiring
REPO
Switch
(NC)
REPO
Switch
(NO)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are
electrically in common.
Figure 4‐20. Normally‐Closed and Normally‐Open REPO Switch Wiring
Twisted
Wires
Twisted
Wires
S
P-164000563 Rev 1 www.eaton.com/powerquality
UPS SYSTEM INSTALLATION
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)
1 (NC)
2 (Return)
UPS TB1
3 (NO)
4 (Return)
4-25