Eaton Power Xpert 9395 Installation And Operation Manual page 45

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Figure 13. Remote EPO Switch Dimensions
115.8
[4.56]
114.3
[4.50]
3 3 . . 2 2 . . 4 4 U U P P S S S S y y s s t t e e m m P P o o w w e e r r W W i i r r i i n n g g P P r r e e p p a a r r a a t t i i o o n n
Read and understand the following notes while planning and performing the installation:
Refer to national and local electrical codes for acceptable external wiring practices.
To allow for future kVA upgrades, consider installing a derated UPS using wiring and external overcurrent
protection breakers sized for a fully rated UPS.
To allow for a future upgrade, install a three UPM model using conductors and external overcurrent
protection breakers sized the same as a fully rated 1100 kVA model.
For external wiring, use 90º C copper or aluminum wire. Wire sizes listed in
copper wiring only. If wire is run in an ambient temperature greater than 30º C, higher temperature wire
and/ or larger size wire may be necessary. Wire sizes are based on using the specified breakers.
Wire ampacities are chosen from Table 310-16 of the National Electrical Code
copper wire with a 90º C rating.
Material and labor for external wiring requirements are to be provided by designated personnel.
If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a
single feed with two upstream feeder breakers, must be provided: one for the UPS or rectifier input
breaker (RIB) (if installed) and one for the maintenance bypass input. DO NOT use a single feed or a single
feeder breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass input breaker (BIB)
is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the
maintenance bypass is acceptable for supplying both the UPS and the bypass.
The bypass feed into this equipment uses three or four wires. The rectifier feed into this equipment uses
three wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment
operation.
If the load requires a neutral, a bypass source neutral must be provided.
DO NOT install both a source neutral and a bonding jumper. See
neutral bonding jumper wire sizes. The bonding jumper must be copper wire.
24
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
0.87
[0.22]
88.9
[3.50]
1.57
[0.40]
Needed to
remove key
1/2" Knockout Pattern
(Typical 5 Sides)
Dimensions are in millimeters [inches].
95.3
[3.57]
(Square)
Table 5
through
®
(NEC
®
). Specification is for
Table
5,
Table
6,
Table
7, or
Table 8
are for
Table 8
for