Eaton Power Xpert 9395 Installation And Operation Manual page 59

Ups 1000-1100 kva, for use with three upm 650-825 kva and four upm 1000-1100 kva ups
Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Table 16. Power Cable Conduit Requirements
UPS Model
Power Xpert 9395-
1100/1000
Power Xpert 9395-
1100/11000
Power Xpert 9395-
1100/650
Power Xpert 9395-
1100/750
Power Xpert 9395-
1100/825
See Note 2
NOTE 1 Select conduit taking into consideration the DC input wire sizes listed in
Table
13, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
NOTE 2 Because of the future upgradability to a fully rated 1100 kVA UPS with the addition of the FI-UPM, these conduit sizes are
specified for an 1100 kVA UPS.
NOTE 3 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing: Refer to the notes at the bottom of
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to
Table
required, it is to be supplied by the customer.
Table 17
lists the recommended rating for input circuit breakers.
38
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Voltage
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
400 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
480 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
400 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
480 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
400 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
AC Input to UPS Rectifier
(A, B, C, Ground)
AC Input to Bypass and Output (Four Wire)
480 Vac
(A, B, C, Ground)
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
DC (All
Battery (Positive, Negative, Ground)
ratings)
5,
Table
6,
Table 7
or
Table 8
Number of
Terminal
Wires in Conduit
Table 5
Table 5
Input/Output Ratings and External Wiring Requirements.
for wiring requirements. If an output lockable disconnect is
Minimum
Number of
Conduit
Conduits
Trade Size
4
3
4
3
5
3–1/2
4
3
4
3
5
3
4
3
4
3
3–1/2
5
4
3
4
3
5
3–1/2
4
3
4
3
5
3–1/2
4
3
4
3
3–1/2
5
See Note 1
or
Table
6, the DC terminations listed in
6
5
6
5
4
5
6
5
6
5
5
6
6
5
6
5
5
6