Table 31. Display Menu Operation (Continued)
Function
Sub-function
System Level 0
Function Selection
Setup
Contrast Adjust
Firmware Versions
Identification
Language
Energy Saver System
Storm Detection
Counter
Storm Detection Timer The Storm Detection Timer screen sets the length of time that power line disturbances are
High Alert Timer
Operation
This screen can be used to set the screen contrast, show the firmware versions installed,
identify the unit type, change the display language, set up Energy Saver functions, set up
Advanced Power Management functions, and enter a password to access Level 1
functions. Press the SETUP pushbutton on the main menu bar to display the System Setup
Level 0 Screen. No password is necessary to access Level 0 functions. Use the up or down
arrow pushbutton to highlight the setup function screen desired, then press the SELECT
pushbutton to display the function screen.
Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust
screen. Use the left or right arrow pushbutton to adjust the contrast for the LCD. When the
contrast adjustment is complete, press the SAVE pushbutton. Once the setting is saved,
the System Setup screen displays. To return to the System Setup screen without saving
the setting, press the ESC pushbutton.
The Versions screen provides the firmware version numbers installed on the UPS. Select
VERSIONS from the System Setup Level 0 menu to display the Versions screen. To scroll
through the firmware types, press the up or down arrow pushbutton on the menu bar. To
return to the System Setup screen, press the ESC pushbutton.
The Unit Type screen provides the model, CTO, and serial numbers of the UPS unit. Select
UNIT TYPE from the System Setup Level 0 menu to display the Unit Type screen. To
return to the System Setup screen, press the ESC pushbutton.
The Language Setup screen allows the display menu language to be set. Select
LANGUAGE SETUP from the System Setup Level 0 menu to display the Language Setup
screen. Use the up or down arrow pushbutton to highlight the desired language, then
press the SELECT pushbutton. To return to the System Setup screen, press the ESC
pushbutton.
The Energy Saver System Setup screen allows the Energy Saver function to be configured.
Select ENERGY SAVER SYSTEM SETUP from the System Setup Level 0 menu to display
the Energy Saver System Setup screen. Use the up or down arrow pushbutton to highlight
the desired function, then press the SELECT pushbutton. To return to the System Setup
screen, press the ESC pushbutton.
The Storm Detection Counter screen sets the number of power line disturbances that can
occur before the UPS locks into Online (Online) mode. Select STORM DETECTION
COUNTER from the Energy Saver System Setup screen to display the Storm Detection
Counter screen. Use the up or down arrow pushbutton to set the counter. Press SAVE or
ABORT. Once the action is completed, the Energy Saver System Setup screen is
displayed.
monitored. The time can be set in 10 minute increments from 0 to 990 minutes. Select
STORM DETECTION TIMER from the Energy Saver System Setup screen to display the
Storm Detection Timer screen. Use the up or down arrow pushbutton to set the time. Press
SAVE or ABORT. Once the action is completed, the Energy Saver System Setup screen is
displayed.
The High Alert Timer screen sets the length of time the UPS remains in Online mode
before transferring back to Energy Saver System mode. The time can be set in 10 minute
increments from 0 to 990 minutes. Select HIGH ALERT TIMER from the Energy Saver
System Setup screen to display the High Alert Timer screen. Use the up or down arrow
pushbutton to set the time. Press SAVE or ABORT. Once the action is completed, the
Energy Saver System Setup screen is displayed.