Interface configuration COM6
For communication via Instance-F, the serial interface COM6 must be operated
with parameters 38400 baud, 8 bits, parity None and 1 stop bit as well as the oper-
ating mode Universal Modbus master. These can be found in IB serial interfaces in
coordinates IB31 to IB33.
Notice
COM6 is then no longer available for communication with a gas chromato-
graph. Therefore, the Modbus Master communication for GC1 and GC2 in
the coordinates IL50 and IL51 must be realized via the serial interface
COM7.
It has to be deactivated if no Modbus IP is used.
Fig. 8.25: Operating mode: Modbus serial C7
Fig. 8.24: Interface configuration COM6
Fig. 8.26: Operating mode: OFF