Part 2: Review on Replacement of MR-J2S-_A_ with MR-J4-_A_
MR-J2S-_A_
No.
Name and function
51
Function selection 6
Used to select the operation method when RES (Reset)
is ON. This parameter is disabled (base circuit shut-off)
by the absolute position detection system.
0
0
0
Action when RES (reset) is turned ON
0: Base circuit shut-off
1: No base circuit shut-off
53
Function selection 8
Used to select the serial communication protocol.
0
0
Protocol checksum selection
0: Yes (Add checksum)
1: No (Do not add checksum)
Protocol station number selection
0: With station numbers
1: No station numbers
Initial
No.
value
0000h
PD30 Function selection D-1
Used to select the base circuit status when RES
(Reset) is ON.
0
0
0
Set the same value as for MR-J2S-_A_.
0000h
No corresponding parameter
Note: MR-J4-_A_
Protocol station No. selection: Supported
Protocol check selection: Supported
2 - 37
MR-J4-_A_
Name and function
Action when RES (reset) is
turned ON
0: Base circuit shut-off
1: No base circuit shut-off
Control
Initial
mode
value
0000h
P
S
T

Hide quick links: