6.6 Cautions

(1) When the maximum value and minimum value of the stored stroke limit's prohibited range are set
to the same value, note that the following will occur.
(a) When the maximum value and minimum value are set to 0, if the outside is the prohibited
(b) If data other than 0 is set for the maximum value and minimum value, the entire range will be
(2) When using indexing axis for C64T, inside of the specified range will be prohibited if the "#2013
OT-" value is larger than that of "#2014 OT+".
(3) The stored stroke limit IC is valid when the axis parameter #2063 is changed.
If changed during automatic operation, the function will be validated after the smoothing for all
axes reaches 0.
(4) Make sure that the lower limit value of the stored stroke limit IC setting value is smaller than the
upper limit value.
(5) The axis parameters #2061, #2062 and #2063 can be changed with DDB.
Downloaded from
ManualsNet.com
range, the entire range will be prohibited. If the inside is the prohibited range, the entire
range will be the moveable range.
the moveable range.
search engine
6. Stored Stroke Limit
6.6 Cautions
III - 43