Advertisement

5. CS16 (TECHLINE
)
®
As the CS16 are open PCB's, they have to be installed in an encapsulation to prevent damage . (LINAK
Adjustment of CS16
The CS16 has a rotary potentiometer for adjusting the value of the cut-off current . To obtain the correct cut-off current, connect the CS16 and turn the
potentiometer as far as it will go/anticlock wise to set the maximum cut-off current .
Then subject the actuator to the maximum load it will be exposed to in the application . At the same time turn the potentiometer clockwise, reducing the
cut-off current, until the actuator stops (not in end position) .
Then turn the potentiometer approx . quarter of a turn anti-clockwise and the system is ready for use .
As the CS16 is a open PCB's, it have to be installed in an encapsulation to prevent damage . (LINAK
6. DJB (MEDLINE
CARELINE
®
Usage
• Compatibility:
• Operating temperature:
• Storage temperature:
• Relative humidity:
• Atmospheric pressure:
• Operational meters above sea level:
• Latex free:
• Approvals:
The CS16 electronic limit switch is connected between the LINAK
it cuts out the current to the actuator in end position of if an obstacle is encountered . The PCB contains a variable
current limit setting and is available in different versions, depending on the actuator with which it is to be used .
The CS16 should be connected between the linear actuator and the power supply, where it will switch off the
power when the actuator reaches end position or if the actuator is overloaded .
)
®
The DIN Junction Box is designed for use where there is a need for more than 1 or 2 controls to be connected to a
control box .
The DIN Junction Box is constructed for connection of up to 4 controls with 8-pin DIN plugs . Furthermore, the box is
constructed so that all channels for connetion are placed on the same side of the box .
This gives the box a clean design and makes it easy to mount e .g . in a bed frame .
CB8, CB9, CB12, CBJ and OpenBus™ control boxes
+5 C to +40 C
-10 C to + 50 C
20% to 80% non-condensing
700 to 1060 hPa
Max . 3000 meters
Yes
IEC 60601-1
ANSI/AAMI ES60601-1
CSA CAN/CSA-C22 .2 NO . 60601-1
IEC 62366
Page 216 of 295
®
actuator and a non-LINAK power supply, where
offers one type of encapsulation for CS16).
®
®
offers one type of encapsulation) .