[SENSe:]FUNCtion:CUSTom:TCouple

Parameters
Comments
Usage
Chapter 6
[SENSe:]FUNCtion:CUSTom:TCouple < type >,[< range >,](@< ch_list >)
channels with the custom Engineering Unit Conversion table loaded with the
DIAG:CUST:PIECE command. The table is assumed to be for a thermocouple and
the <type> parameter will specify the built-in compensation voltage table to be used
for reference junction temperature compensation. SENS:FUNC:CUST:TC allows
you to use an EU table that is custom matched to thermocouple wire you have
characterized. Contact your Hewlett-Packard System Engineer for more information
on Custom Engineering Unit Conversion for your application.
Parameter
Parameter
Name
Type
type
discrete (string)
range
numeric (float32)
ch_list
channel list (string)
See "Linking Input Channels to EU Conversion" on page 64..
The <range> parameter: The HP E1415 has five ranges: .0625VDC, .25VDC,
1VDC, 4VDC, and 16VDC. To select a range, simply specify the range value
(for example, 4 selects the 4VDC range). If you specify a value larger than
one of the first four ranges, the HP E1415 selects the next higher range (for
example, 4.1 selects the 16VDC range). Specifying a value larger than 16
generates an error. Specifying 0 selects the lowest range (.0625VDC).
Specifying AUTO selects auto range. The default range (no range parameter
specified) is auto range.
If you are using amplifier SCPs, you should set them first and keep their
settings in mind when specifying a range setting. For instance, if your expected
signal voltage is to be approximately .1VDC and the amplifier SCP for that
channel has a gain of 8, you must set <range> no lower than 1VDC or an input
out-of-range condition will exist.
The sub_type EEXTended applies to E type thermocouples at 800°C and
above.
The *CAL? command calibrates temperature channels based on Sense
Amplifier SCP setup at the time of execution. If SCP settings are changed,
those channels are no longer calibrated. *CAL? must be executed again.
Related Commands: DIAG:CUST:PIEC, *CAL?,SENS:REF, and
SENS:REF:TEMP
*RST Condition: all custom EU tables erased
program must put table constants into array table_block
DIAG:CUST:PIEC 1,table_block,(@100:107) send characterized thermocouple table
Range of
Values
E | EEXT | J | K | N | R | S | T
see comments
100 - 163
HP E1415 Command Reference
[SENSe]
links
Default
Units
none
VDC
none
245