10.3.4.1.2 Configuring Parameters

The OPC UA server provides nodes with configuration parameters for the device. For ex-
ample, the OPC UA client can read out the upper limiting value for temperature in the
OverTemperature node. The path to this node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > Diag-
nostics > Configuration
The following table lists device-specific configuration parameters.
Node Name
CurrentHysteresis
OverTemperature
OverVoltageL
OverVoltageL2
TemperatureHysteresis
UnderTemperature
UnderVoltageL
UnderVoltageL2
VoltageHysteresis
The OPC UA server provides nodes with configuration parameters for each port. The
path to this node is:
Root > Object > DeviceSet > [device name] > IOLinkMaster > Diag-
nostics > PortXX > Configuration
The following table lists port-specific configuration parameters.
Node Name
OverCurrentPin1, Over-
CurrentPin2, OverCur-
rentPin4
UnderCurrentPin1, Un-
derCurrentPin2, Under-
CurrentPin4
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
Node Class
Access Default Description
Variable
Read
10 mA
Variable
Read
70 °C
Variable
Read
30 V
Variable
Read
30 V
Variable
Read
2 °C
Variable
Read
−25 °C Lower limiting value for the temperature of a port;
Variable
Read
18 V
Variable
Read
18 V
Variable
Read
300 mV Voltage hysteresis; unit: mA
Node Class
Access Default Description
Variable
Read
0
Variable
Read
0
Table 62: Device-Specific Configuration Parameters
Current hysteresis; unit: mA
If the current exceeds the limiting value, the cur-
rent must fall back below the limiting value by the
hysteresis to revoke the diagnosis.
Upper limiting value for the temperature of a port;
unit: 0.1 °C
Upper limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
Upper limiting value for the voltage in supply ca-
ble 2; unit: mV
Temperature hysteresis; unit: 0.1 °C
If the temperature exceeds the limiting value, the
temperature must fall back below the limiting
value by the hysteresis to revoke the diagnosis.
unit: 0.1 °C
Lower limiting value for the voltage in supply ca-
ble 1; pins with the following functions can be
monitored: L+, DI, DO, DIO, IO-Link; unit: mV
Lower limiting value for the voltage in supply ca-
ble 2; unit: mV
If the voltage exceeds the limiting value, the volt-
age must fall back below the limiting value by the
hysteresis to revoke the diagnosis.
Table 63: Port-Specific Configuration Parameters
Warning level for current upper limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled
Warning level for current lower limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled