Functions

Functions
5

5.1 Process Image

EtherCAT
transferred from the EtherCAT
0x1601 etc.; these data objects are called receive PDOs (RxPDOs). Process data is
transferred from the EtherCAT
0x1A01 etc.; these data objects are called send PDOs (TxPDOs).
Input Process Data
The 0765-4203/0100-0000 module uses multiple TxPDOs for transferring input process
data:
• One object 0x1A0x per port with the IO-Link input data or the value of the digital input
• Object 0x1A10 for transferring the digital inputs of all ports
• Object 0x1A11 with status "New Message Available"
• Object 0x18A0 with the status of the IO-Link ports
Input Process Data
The 0765-4203/0100-0000 module uses multiple RxPDOs for transferring output process
data:
• One object 0x160x for each port with the IO-Link output data or the value of the digital
output
• Object 0x1610 for transferring the digital outputs of all ports (pin 2 in each case)
Input Process Data
Objects 0x1A0x:
The content of objects 0x1A00 to 0x1A03 depends on the operating mode settings of the
corresponding ports. Object 0x1A0x contains the port operating modes "IO-Link" and
"Digital input." The assignment is as follows:
• Object 0x1A00 is assigned to port X01.
• Object 0x1A01 is assigned to port X02.
• Object 0x1A02 is assigned to port X03.
• Object 0x1A03 is assigned to port X04.
Objects 0x1A0x with port operating mode "IO-Link":
The following table describes the assignment of input process data to port for the "IO-
Link" port operating mode.
Index Subindex
0x6000.01
0x6000.02
...
0x6000.20
24
Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A
®
uses process data objects (PDO) to transfer process data. Process data is
®
master to the EtherCAT
®
slave to the EtherCAT
Size
1 byte
1 byte
...
1 byte
®
slave with objects 0x1600,
®
master with objects 0x1A00,
Table 19: Objects 0x1A0x: Assignment of the IO-Link input data
Name
Description
Input byte 0
Object 0x1A00 with input process data of
port X01
Input byte 1
IO-Link input data of the IO-Link device on
...
port X01. For a description of the data, see
Input byte 31
the manual from the manufacture of the IO-
Link device used.
765-4203/0100-0000